Which products are affected by Ecodesign ?
The European Union has developed two directives ( Ecodesign Directive 2009 / 125 / EC and Energy Labeling Directive 2010 / 30 / EC ) to address the environmental impact of all Energy related Products ( ErP ) beginning at the earliest stages of design . The Ecodesign directive affects all types of Energy related Products ( ErP ) such as TVs , washing machines , lights and , of course , also HVAC products and components . Energy related Products ( ErP ) are grouped into “ Lots ” that , once they are published , they become mandatory CE regulations . There are three Ecodesign Lots ( already approved regulations ) that directly impact HVAC products .
¢ ENER Lot 21 ð Reg 2016 / 2281 ð Central Heating and Cooling Products ( Chillers ) ¢ ENTR Lot 1 ð Reg 1095 / 2015 ð Professional Refrigeration ( Process Chillers Brine ) ¢ ENER Lot 1 ð Reg 813 / 2013 ð Space Heaters ( Heat Pumps )
Each of the three regulations set the MEPS or Minimum Efficiency Performance Standards for the product category and those are implemented in 2 steps ( Tiers ), as shown in the table below .
ECODESIGN EU Framework Directive 2009 / 125 / EC
Sets the General Rules
Regulation Scope MEPS 2015 2016 2017 2018 2019 2020 2021
Reg 2016 / 2281 ( former ENER Lot 21 )
Reg 1095 / 2015 ( former ENTR Lot 1 )
Reg 813 / 2013 ( former ENER Lot 1 )
Comfort Chillers SEER ηs , c High Temperature Process Chillers
Medium Temperature Process Chillers
SEPRHT
SEPRMT
Heat Pumps SCOP ηs , h
T1 Oct15
T1 Jul16
T2 Oct17
T1 Jan18
T2 Jul18
T2 Jan21
Calculations according to Transitional Methods that indicates the Harmonized EN standards to use ( EN14511 , EN14825 mainly ).
Ecodesign has changed the way we speak
Former full efficiency ratios like EER and COP are now disappearing . Even the seasonal efficiency ratio ESEER has been replaced . Ecodesign MEPS are the current key indicators used for all HVAC product and compliance is mandatory to have the CE marking . The Eurovent organization is already using Ecodesign MEPS at the different certification programs are not using ESEER value anymore .
BEFORE Ecodesign AFTER Ecodesign
EER
COP
|
ESEER |
SEPR
SEER
SCOP
|
SEPR Is the new performance indicator for chillers in industrial process cooling applications .
SEER Is the new performance indicator for chillers in comfort cooling applications .
SCOP Is the new performance indicator for space heating applications .
|
η s , c
η s , h
|
Eta s ( η s ):
Ecodesign introduces a new performance indicator for seasonal primary energy efficiency that allows product efficiency comparison with different energy sources .
|
Calculation method An important point that must be specified on the manufacturers rating report is the calculation method regarding the water flow and outlet temperature . According regulation there are four possible methods .
FW / FO = Fixed Water Flow , Fixed Outlet Temperature FW / VO = Fixed Water Flow , Variable Outlet Temperature
VW / FO = Variable Water Flow , Fixed Outlet Temperature VW / VO = Variable Water Flow , Variable Outlet Temperature
• Variable Outlet allows to change the leaving water temperature at partial load . This reduces the lift required by the chiller , reducing energy use significantly . To provide this rating , chillers must be capable of automatic water temperature reset based on outdoor ambient temperature . With this capability , even projects without advanced building control systems can benefit .
• Variable Flow reduces energy use at part load through reduced waterside pressure drop . Variable Speed Pumps must be fitted to the system to benefit from this savings .
• It is important to note that efficiencies can vary hugely depending on the temperatures and the method of calculation .
• It is crucial to check the chilled water conditions used to determine the SEER , SEPR and SCOP when comparing the seasonal energy efficiency .
YORK Air-Conditioning Products 115