42BJ ICM
Physical and electrical data
42BJ ICM LEC
Fan speed*
Air flow
Available static pressure
Cooling mode**
Total cooling capacity
Sensible cooling capacity
Water flow rate
Water pressure drop
Water content
Two-pipe heating mode***
Heating capacity
Eurovent energy class FCEER/FCCOP
Four-pipe heating mode****
Heating capacity
Water flow rate
l/s
m3/h
Pa
1.9
L
16
56
1
M
145
521
50
H
201
722
97
2.9
L
24
88
1
M
160
575
50
H
223
803
99
4.9
L
28
101
3
M
148
534
50
H
204
733
92
kW
kW
l/s
l/h
kPa
l
0.45
0.36
0.02
80
2
0.9
2.99
2.34
0.12
448
27
0.9
3.74
3.00
0.17
628
47
0.9
0.66
0.46
0.03
118
2
1.2
3.95
2.91
0.19
699
39
1.2
5.26
3.95
0.25
912
61
1.2
1.12
0.75
0.06
224
5
1.5
3.94
2.78
0.25
884
61
1.5
4.91
3.53
0.26
935
68
1.5
kW
0.51
C/C
3.56
4.45
0.75
B/B
4.72
6.33
1.19
B/B
4.53
5.77
kW
l/s
l/h
kPa
l
0.62
0.02
60
1
0.2
C/C
230-1-50
0.5
11
3.12
0.07
267
15
0.2
3.70
0.10
348
23
0.2
1.08
0.03
94
4
0.29
B/B
4.30
0.10
376
32
0.29
5.18
0.12
449
41
0.29
1.87
0.05
168
8
0.45
B/A
5.47
0.15
550
67
0.45
6.54
0.16
577
73
0.45
2.25
11
1
11
2.25
11
2.25
11
59
69
69
48
43
32
31
34
13
-
56
65
65
44
39
61
72
72
51
46
174
5
315 x 550
46
186
Water pressure drop
Water content
Eurovent energy class FCEER/FCCOP
V-ph-Hz
Electric heater
Maximum capacity
kW
1.9
2.23
0.75
2.12
Maximum current drawn
A
11
11
11
11
Sound levels
Sound power level (return + radiated)
dB(A)
29
53
59
34
52
Sound power level (supply)
dB(A)
26
59
66
20
63
Global sound power level
dB(A)
31
61
67
34
63
Sound pressure levelâ€
dB(A)
10
40
46
13
42
NR val