RACA Journal November 2026 | Page 33

RACA Journal I November 2026 www. refrigerationandaircon. co. za 31
FEATURE SERIES
production environment, while the slight positive pressure helps establish a defined direction of airflow rather than relying on uncontrolled infiltration.
Once process cooling relies on very large volumes of air, the airflow system itself becomes an important part of the energy equation. Filters, coils, dampers and ductwork all create resistance, while poorly designed airflow paths can increase pressure drop. At approximately 30m ³/ s per air-handling system, even relatively modest increases in resistance can have a significant effect on fan energy over the operating life of the installation.
This is where process cooling, energy efficiency and acoustics begin to converge.
DESIGNING OUT NOISE The following is derived from ASHRAE Journal podcast no. 60. With such large air volumes, acoustics becomes part of the airflow design. Smooth duct transitions, appropriate duct sizing and gradual changes in direction reduce turbulence, pressure drop and associated noise.
This means fan selection is equally important. An installation can use multiple electronically commutated plug fans, allowing airflow to be matched more closely to the actual requirement. This avoids continuously moving the maximum design volume when production or ambient conditions do not require it, reducing both energy consumption and noise.
Acoustic treatment can provide further noise reduction, but silencers and other components also add resistance to the airstream. The objective is therefore to design the system for low turbulence and low pressure drop from the outset, rather than relying on acoustic treatment to correct an inherently noisy airflow system.
CONTROLS COMPLETE THE SYSTEM Energy efficiency extends beyond the use of free cooling. A PLC-based control system allows the installation to respond to changing ambient and process conditions. Free cooling is not simply a matter of introducing outside air whenever it is cooler than the indoor environment. Temperature, humidity, production
conditions and the required production environment all have to be considered.
The controls determine when outside air can provide the required cooling, when mechanical cooling is necessary and how much airflow is required. Refrigeration can therefore be used selectively rather than continuously.
The same principle applies to the fans. If the required airflow can be reduced while maintaining the necessary production environment, fan power can be reduced at the same time.
A BROADER DEFINITION OF PROCESS COOLING This demonstrates how process cooling can be approached without automatically defaulting to a large conventional air conditioning system.
The key is to understand where heat and moisture originate, how they vary with production and weather conditions, and which loads can be addressed through ventilation, dehumidification, heat recovery and intelligent control.
It also demonstrates that process cooling is not necessarily a single piece of equipment or a refrigeration system. It can be an integrated environmental control strategy in which ventilation, mechanical cooling, air distribution, filtration, heat recovery and controls work together.
The acoustics dimension reinforces this approach. Once large quantities of air become the primary vehicle for removing process heat, fan efficiency, duct design, pressure drop and acoustic performance all become part of the cooling system.
In the above project, effective process cooling is therefore not simply about adding refrigeration. It is about managing the interaction between the manufacturing process, ambient conditions, airflow, temperature and humidity. RACA
REFERENCES:
• ASHRAE Journal podcast no. 60
• ASHRAE Standard 62.1
• CIBSE Guide B – Heating, Ventilating, Air Conditioning and Refrigeration, Chartered Institution of Building Services Engineers
Energy Process artificial efficiency cooling intelligence
A fabric duct delivers cooled, filtered air across the production floor below – the final link that carries process cooling from source to the point where it ' s actually needed.

RACA Journal I November 2026 www. refrigerationandaircon. co. za 31