32 www. refrigerationandaircon. co. za RACA Journal I November 2026
FEATURE SERIES
Energy efficiency
ENERGY EFFICIENCY AND ACOUSTICS: TWO SIDES OF THE SAME AIRFLOW COIN
By Eamonn Ryan
Energy efficiency and acoustics are closely linked in HVAC & R systems.
The same factors that create unwanted noise – turbulence, excessive air velocities, poor duct design and high pressure losses – also increase the energy required to move air. Conversely, smooth airflow paths, low-pressure-drop components, correctly selected fans and effective maintenance not only reduce sound levels but also improve system efficiency. In many cases, a quieter air distribution system is also a more energy-efficient one, making acoustics and energy performance two sides of the same airflow coin.
HOW WE QUIET THE FLOW Whenever air moves through a duct or ventilation system, it generates noise. Over decades of research and development, engineers have developed three broad approaches to controlling that sound. Although many examples originate in heavy industry, the same principles apply across HVAC & R systems in commercial buildings, hospitals, data centres and transport applications.
The three main categories are:
• Absorptive( dissipative) silencers, which use porous or fibrous materials to absorb sound energy, making them particularly effective at reducing mid- and high-frequency noise.
• Reactive silencers( Helmholtz resonators), which use carefully tuned chambers to cancel specific sound frequencies, making them especially useful for controlling low-frequency fan and duct noise.
• Hybrid silencers, which combine absorptive and reactive technologies to provide broad-spectrum noise attenuation across a wide range of frequencies.
At the 2026 Howden Technology Day, Raul Ferreira, senior applications engineer at Howden, a Chart Industries company, explained how understanding the relationship between airflow and acoustics enables engineers to design systems that are not only thermally efficient but also significantly quieter.
HOW TURBULENCE BECOMES NOISE At the heart of this relationship is turbulence. When air flows smoothly along a well-designed path at sensible speeds, it tends to be relatively quiet. Problems arise when airflow is forced through sharp bends, abrupt expansions or restrictive passages. The resulting turbulence creates fluctuating pressure fields that we perceive as noise.
In large air systems, turbulence creates two main forms of noise: vibration of ducts and casings(‘ breakout noise’) and the sound generated by turbulent discharge air. Both become more pronounced when fans operate well away from their design point.
Not all of this noise sounds the same. Low-frequency noise from large fans and ducts travels long distances and is difficult to attenuate, while higher-frequency hiss is easier to absorb but often more immediately irritating. Effective acoustic design therefore depends on understanding which frequencies dominate a particular system. The same turbulence that generates unwanted noise also increases system resistance and pressure losses. In effect, noise is often an audible indication that energy is being wasted as airflow departs from its optimal path.
THREE APPROACHES TO CONTROLLING AIRFLOW NOISE Ferreira began by discussing absorptive silencers. Sound entering the porous material is dissipated as tiny amounts of heat, making these silencers particularly effective at reducing mid- and highfrequency noise.
Raul Ferreira, senior applications engineer at Howden.
The catch with absorptive solutions is that the material is usually sitting directly in the airstream. In clean, well-filtered systems this is not a major concern. In dustier or more aggressive environments, the pores become clogged, the surface roughens and the acoustic performance gradually fades. Over time, a onceeffective silencer can become little more than a slightly narrower piece of ductwork unless it is regularly cleaned or replaced. In that