30 www. refrigerationandaircon. co. za RACA Journal I November 2026
FEATURE SERIES
Process cooling
The cooling coil provides dehumidification as part of the ventilation process by deliberately cooling a proportion of the air sufficiently to remove moisture.
This highlights the difference between comfort air conditioning and process-environment cooling. The objective is not necessarily to maintain a conventional comfort setpoint throughout the production area. Instead, the system must manage the conditions that matter to the manufacturing environment using the least energy intensive means available.
The cooling strategy therefore responds to both the process and the weather. When outdoor air can absorb and carry away process heat, it becomes the primary cooling medium. When ambient conditions are no longer favourable, mechanical cooling supplements the ventilation system.
Rooftop air handling units and refrigerant / condenser components— the mechanical backbone of process cooling, engaged when ambient conditions alone aren ' t enough to hold temperature and humidity within spec.
TURNING PROCESS HEAT INTO A RESOURCE The strategy also changes with the season. During winter, heat generated by production becomes a useful resource rather than simply a problem. Warm air associated with the shrink-wrapping process can be recovered and redirected through the system, reducing the need for dedicated heating.
This illustrates a broader principle of industrial environmental control: process heat does not always have to be rejected. Depending on the season and operating conditions, it can become a useful source of heat elsewhere in the facility. The design therefore considers not only how much heat is generated, but where it originates, when it occurs, how it moves through the space and whether it can be removed or reused.
DISTRIBUTION IN A LIVE FACTORY Air distribution presented another challenge. The existing factory was not designed to accommodate extensive heavy ductwork, while the production floor contained significant quantities of equipment and had limited available space.
Lightweight fabric ducting was therefore selected. Suspended with relatively little structural support, the fabric ducts could deliver the required high air volumes while minimising the impact on the existing building. The choice was also important to the cooling strategy itself. At high airflow rates, the way air is introduced into the production space influences mixing, local air velocities and the effectiveness of heat removal. The distribution system has to remove heat from the occupied production environment without creating excessive drafts or allowing supply air to short-circuit directly to the extraction points.
Filtration is similarly integral to the system. G4 and F7 filters provide staged filtration of incoming air before it reaches the