www. refrigerationandaircon. co. za 29
FEATURE SERIES
PROCESS COOLING IN THE FMCG MANUFACTURING ENVIRONMENT
By Eamonn Ryan
Process cooling in a food and fast-moving consumer goods( FMCG) manufacturing environment is not necessarily about directly cooling machinery or a production line. In many facilities, the greater challenge is controlling the heat, humidity and air quality generated by the manufacturing process itself.
Energy Process artificial efficiency cooling intelligence
All images by © RACA Journal recent HVAC retrofit in a live FMCG production facility
A( to be published as a project in the near future) illustrates how this can be achieved without relying on a conventional full mechanical cooling installation. The project used high-volume fresh air to remove process heat, supplemented by targeted mechanical cooling when ambient conditions required it.
The starting point was a familiar industrial problem: the production area had become excessively hot and humid. A significant proportion of the sensible heat came from heated shrink-wrap tunnels operating continuously as part of the packaging process. These effectively function as large electric heating elements, releasing substantial heat into the surrounding environment. Process-related moisture added a latent load, making conditions uncomfortable for personnel and complicating environmental control.
COOLING THROUGH AIRFLOW The production area was divided into two zones, each served by a dedicated air-handling system. Each system supplies approximately 30m ³/ s of filtered fresh air, with extraction of around 28m ³/ s. The slight difference between supply and extraction creates positive pressure within the production environment, helping to limit the infiltration of dust and untreated outside air.
Stainless-steel process tanks and pipework on the production floor— the kind of internal heat-generating equipment that process cooling systems are designed to offset, keeping ambient conditions within workable limits despite the wall display reading 27 ° C.
RACA Journal I November 2026
The high air volume is central to the cooling strategy. Instead of relying principally on recirculated conditioned air, the system uses outdoor air whenever conditions are favourable. For much of the year, this allows heat generated by the manufacturing process to be removed through ventilation rather than refrigeration.
This is essentially a free-cooling strategy. When outdoor conditions are suitable, 100 % fresh air can be introduced without significant mechanical cooling, reducing the operating hours and energy consumption of the refrigeration system.
Mechanical cooling becomes necessary when ambient temperatures rise sufficiently for ventilation alone to become inadequate. In this installation, that generally occurs at outdoor temperatures of approximately 28 – 30 ° C.
Even then, refrigeration is used selectively rather than being sized to overcome the entire building load. Each air handling unit incorporates a cooling coil with a capacity of approximately 283kW. Bypass dampers allow the quantity of air passing over the coil to be controlled, with approximately half of the incoming air passing through the cooling section and the remainder bypassing it.
This arrangement also provides dehumidification. Air passing over the coil is cooled to approximately 13 ° C, below its dew point, causing moisture to condense on the coil. The cooled, dehumidified air is then mixed with the bypassed air to achieve the required supply condition.
The result is a system capable of addressing both temperature and humidity without mechanically cooling the entire air volume. It also permits a smaller cooling coil than would otherwise be required, reducing equipment size, weight and capital cost.
HUMIDITY IS PART OF THE COOLING LOAD Humidity is an important consideration in FMCG manufacturing. Large quantities of fresh air can introduce substantial moisture when outdoor conditions are humid. Simply increasing ventilation could therefore improve temperature conditions while making humidity control more difficult.
www. refrigerationandaircon. co. za 29