Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 84
Base
material
Type of joint — description
Fire
rating
(F rating)
Max. joint
width
(inches)
Movement
capability
Hilti product
used
System
number Sealant
depth
(inches)
See
page
> Floor to floor, wall to floor and wall to wall joints (continued)
Gypsum wall to concrete floor (bottom of wall) 1 or 2 hr 3/4" - CP 601S,
CP 606,
FS-ONE,
CFS-S SIL GG,
CP 605 BW-S-0002 5/8" 573
G Gypsum shaft wall to concrete floor (bottom of wall) 1 or 2 hr 1" - CP 606,
CP 605 BW-S-0023 * 574
G Gypsum wall to concrete floor (bottom of wall) 1 or 2 hr 3/4" - CFS-TTS BW-S-0039 - 575
G Gypsum wall to non-rated roof deck (top-of-wall
continuity joint) 2 hr 1-1/2" 50% CFS-SP WB CJ-D-0004 1/8" 576
G Gypsum wall to column 1 or 2 hr 1-1/2" - CFS-SP WB HI/JF 120-01 1/8" 577
G Gypsum wall perpendicular to concrete over metal
deck with optional use of spray-on fireproofing
(includes roof deck) (top-of-wall) 1 or 2 hr 1" 50% CFS-SP WB HW-D-0042 1/8" 579
G Gypsum wall perpendicular to concrete over metal
deck (includes roof deck) (top-of-wall) 1 or 2 hr 3/4" 33% CP 606 HW-D-0045 1/2" 581
G Gypsum wall parallel to concrete over metal deck
with optional use of spray-on fireproofing (includes
roof deck) (top-of-wall) 1 or 2 hr 1" 50% CFS-SP WB HW-D-0049 1/8" 582
G Gypsum wall to concrete over fluted metal deck (top-
of-wall) 1 or 2 hr 3/4" 17% CP 606 HW-D-0077 5/8" or
1-1/4" 584
G Gypsum wall to concrete floor or hollowcore (top-
of-wall) 1 or 2 hr 3/4" 17.00% CP 606 HW-D-0083 5/8" or
1-1/4" 585
G Gypsum wall parallel to concrete over metal deck
with optional use of spray-on fireproofing (includes
roof deck) (top-of-wall) (sealant only) 1 or 2 hr 3/4" 17% CP 606 HW-D-0184 5/8" 586
G Gypsum wall to concrete floor or hollow core
concrete (top-of-wall) 1 or 2 hr 3/4" 17% CP 606 HW-D-0209 5/8" 587
G Gypsum wall parallel to concrete over metal deck
with spray-on fireproofing (top of wall) (beam/bar
joist through joint) 1 or 2 hr 1" 25% CFS-SP WB HW-D-0218 1/8" 588
G Gypsum wall to underside of steel beam and
concrete over metal deck with spray-on fireproofing
(top-of-wall) 1 or 2 hr 1" 50% CFS-SP WB HW-D-0259 1/8" 590
G Gypsum wall parallel to concrete over metal deck
(wall not centered under lower plane of flute) (top of
wall) 1 or 2 hr 1" 18.75% CFS-SP WB HW-D-0264 1/8" 592
G Gypsum shaft wall to concrete floor (top of wall) 2 hr 3/4" 8% CP 606 HW-D-0342 1" 594
G Top of gypsum wall assembly to concrete over metal
deck floor/roof assembly 1 or 2 hr 1" 12.50% CFS-SP WB HW-D-0388 1/8" 595
G Gypsum Wall to concrete over metal deck (offset to
flute) 1 or 2 hr 3/4" 17.00% CFS-SP WB,
CP 606 HW-D-0396 1/8" 597
G Gypsum wall to concrete over metal deck (top-of-
wall) (perpendicular) 1 hr 2" 20.00% CFS-SP WB HW-D-0564 1/8" 599
G Gypsum wall to underside of fireproofer steel I beam 1 or 2 hr 1/2” 50% CFS-SP WB HW-D-0634 1/8” 601
G Gypsum Shaft Wall to concrete over metal deck
(perpendicular/parallel) or concrete floor/hollow core 1 or 2 hr 1-1/2" 25% CFS-SP WB HW-D-0750 1/8" 603
G Gypsum wall to concrete over concrete floor (top-of-
wall) (perpendicular) 1 or 2 hr 3/4" 50% CFS-TTS HW-D-0757 * 606
G Gypsum wall perpendicular to fluted metal deck 1 or 2 hr 2-1/2" 40% CFS-SP WB HW-D-1066 1/8" 607
G
Hilti Firestop
Saving lives
through innovation
and education
82
* Refer to UL System.
C
Concrete or concrete block
G
Gypsum
W
Wood