Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 83
Firestop Selection Chart
JOINT
Fire
rating
(F rating)
Type of joint — description
Max. joint
width
(inches)
Movement
capability Hilti product
used System
number Sealant
depth
(inches) See
page
> Floor to floor, wall to floor and wall to wall joints
14% CFS-SP WB FF-D-1013 1/8" 544
C Concrete floor to floor joint 2 hr 6" 10% CFS-S SIL SL FF-D-1039 1/2" 547
C Concrete floor to floor joint 4 hr 3" 12.50% CFS-S SIL SL FF-D-1125 1/2" 546
C Concrete floor to floor joint 2 hr 3" 33.00% CFS-S SIL SL,
CFS-S SIL GG FF-D-1126 1/4" 547
C Concrete floor to wall joint 2 hr 3-1/2" 14% CFS-SP WB FW-D-1013 1/8" 548
C Concrete floor to wall joint 2 hr 6" 10% CFS-S SIL SL FW-D-1037 1/2" 549
C Concrete floor to wall joint 2 hr 3" 17% CP 606 FW-D-1071 1/4" 550
C Concrete floor to wall joint 2 hr 3" 33% CFS-S SIL SL,
CFS-S SIL GG FW-D-1093 1/4" 551
C Concrete or block wall perpendicular and parallel to
concrete over metal deck (includes roof deck) (top
of wall) 2 hr 3/4" 33% CP 606 HW-D-0081 1/2" 552
C Concrete or block wall to concrete over fluted metal
deck (top-of-wall) 1 or 2 hr 1" 12.50% CFS-SP WB HW-D-0098 1/8" 553
C Concrete or block wall to concrete over metal deck
with optional use of spray-on fireproofing (parallel)
(top-of-wall) 2 hr 1" 12.50% CFS-SP WB HW-D-0181 1/8" 555
C Concrete or block wall parallel to concrete over
metal deck with spray-on fireproofing (I beam/bar
joist through joint) (top of wall) 2 hr 1" 25% CFS-SP WB HW-D-0258 1/8" 556
C Concrete or block wall to concrete floor or hollow
core floor (Sealant only) (top of wall) 2 hr 1" 12.50% CP 606 HW-D-0268 1/2" 558
C Concrete or block wall perpendiular to concrete over
metal deck (includes roof deck) (top of wall — one
side access) 2 hr 2" 12.50% CFS-SP WB HW-D-0285 1/8" 559
C Concrete or block wall parallel to concrete over
metal deck (includes roof deck) (top of wall - one
side access) 2 hr 2" 12.50% CFS-SP WB HW-D-0286 1/8" 556
C Top of concrete or block wall to fluted steel roof deck 2 hr 1" 12.50% CFS-SP WB HW-D-0389 1/8" 561
C Concrete or block wall to bottom of fire-proofed
steel I-beam to concrete over metal deck 2 hr 2" 12.50% CFS-SP WB HW-D-0440 1/8" 563
C Concrete or block wall perpendicular to concrete
over metal deck with optional use of spray-on
fireproofing (top of wall) 2 hr 3-1/2" 14% CFS-SP WB HW-D-1037 1/8" 564
C Concrete or block wall to concrete floor 3 hr 3-1/4" 25% CFS-SP WB HW-D-1058 1/8" 565
C Block wall to underside of flat concrete 2 hr 3" 17% CP 606 HW-D-1078 1/4" 566
C Concrete or block wall to wall joint (sealant only) 2 hr 1" 12.50% CP 606 WW-D-0032 1/2" 567
C Concrete or block wall perpendicular to gypsum wall
(wall to wall) (Sealant only) 1 or 2 hr 3/4" 17% CP 606,
CFS-S SIL GG WW-D-0040 5/8" 568
C Concrete wall to wall joint 2 hr 3" 17% CP 606 WW-D-1080 1/4" 569
C Concrete wall to wall joint 2 hr 3-1/2” 14% CFS-SP WB WW-D-1084 1/8” 570
C Concrete wall to wall joint 2 hr 3" 33% CFS-S SIL GG WW-D-1129 1/4" 571
C Concrete wall to gypsum wall (gyp sitting on top of
concrete) 1 or 2 hr 3/4" - CP 606,
CP 601S,
CFS-S SIL GG WW-S-0048 5/8" 572
3-1/2" 2 hr Concrete floor to floor joint C
Base
material
* Refer to UL System.
C
Concrete or concrete block
G
Gypsum
W
Wood
Hilti Firestop
Saving lives
through innovation
and education
81