Firestop Selection Chart
Base
material
Fire
rating
(F rating)
Type of joint — description
Max. joint
width
(inches)
Movement
capability
Hilti product
used
System
number Sealant
depth
(inches) See
page
2-1/2" 40% CFS-SP WB HW-D-1067 1/8" 608
G Gypsum wall to concrete floor joint or fluted metal
floor/roof deck 1 or 2 hr * - CFS-SP WB HW-S-0053 1/8" 609
G Gypsum wall to concrete floor or fluted metal floor/
roof deck (top-of-wall) 1 or 2 hr * - CP 606 HW-S-0054 1/2" 610
G Gypsum Wall to gypsum ceiling 1 or 2 hr 1/2" - CP 606,
FS-ONE MAX HW-S-0090 5/8" 611
G Gypsum wall to wall joint 1 or 2 hr 2" 12.50% CP 606 WW-D-0067 1/2" 612
G Gypsum shaft wall to concrete wall 1 or 2 hr 1" - CP 606 WW-S-0059 1" 613
G Gypsum wall to concrete wall 1 or 2 hr 3/4" - CFS-TTS WW-S-0074 Tilt-Up Concrete Panel Curtain Wall 2 hr 6" 5% CFS-SP SIL CW-D-1001 1/8" 615
Glass, Aluminum, or Granite Spandrel with
Aluminum Framing 2 hr 4" 5% CFS-SP SIL CW-D-1015 1/8" 617
Concrete floor to glass, aluminum, or granite
spandrel with aluminum framing 2 hr 8" 5% CFS-SP SIL CW-D-2026 1/4" 619
Concrete floor to glass, aluminum, or granite
spandrel with aluminum framing 2 hr 8" 5% CFS-SP WB/
CP 672 CW-D-2027 1/8" 622
Gypsum exterior with various façades with steel
framing 2 hr 9" 0% CFS-SP WB HI/BP 120-03
(CEJ-421-P) 1/8" 625
Gypsum with various facades. Steel framing starts
and stops above and below floor 2 hr 2" - CFS-SP WB HI/BP 120-05 1/8" 629
2-1/2 hr 8" 12.5% &
6.25% CFS-SP WB HI/BP 150-01 1/8" 633
Concrete floor to glass or aluminum spandrel with
aluminum framing 3 hr 8" 11.25% &
5% CFS-SP WB HI/BP 180-01
(CEJ-307-P) 1/8" 636
Steel Back Pan w/Glass Spandrel with Aluminum
Framing 2 hr 6" - CFS-SP WB,
CFS-SP SIL HI/BPF 120-09 1/8"
2mm 640
Steel Back Pan w/Glass Spandrel with Aluminum
Framing 2 hr 4" - CFS-SP WB,
CFS-SP SIL HI/BPF 120-10 1/8"
2mm 643
Glass spandrel with aluminum framing 2 hr 6" - CFS-SP WB HI/JS 120-05
(CEJ-127-P) 1/8" 645
Gypsum with Stone Finish and Steel Framing 2 hr 8" - CFS-SP WB,
CFS-SP SIL HI/PHV 120-07
(CEJ-261-P) 1/8”
2mm 648
614
> Curtain Wall Joints
Glass Spandrel with Aluminum framing (vision glass
at floor)
1 or 2 hr Gypsum wall parallel to fluted metal deck G
> Floor to floor, wall to floor and wall to wall joints (continued)
STEEL PROTECTION
Base
material
Hilti product
used
Description
System
number
See
page
CFP-SP WB BXUV.Y633 670
CFP-SP WB BXUV.Y634 679
For beams CFP-SP WB BXUV.N640 654
For concrete and steel floor units CFP-SP WB BXUV.D990 651
For wide flange steel columns For hollow section columns
* Refer to UL System.
C
Concrete or concrete block
G
Gypsum
W
Wood
Hilti Firestop
Saving lives
through innovation
and education
83