Firestop Selection Chart | Page 41

Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
CABLES IN WOOD-FRAMED FLOORS
Cable bundle ( various cables ) Cable bundle ( various cables ) ( AS = 3 / 4 ”) Cable bundle ( various cables ) ( AS = 0 ” to 1 ”) Cable bundle ( various cables ) ( AS = 0 ” to 1 ”) Multiple SER cables in slotted opening ( AS varies ) Cable bundle ( various cables ) ( AS = min 0 ”)
INSULATED PIPES IN WOOD-FRAMED FLOORS
Max . 2 ” steel or copper pipes with max . 1 / 2 ” glass fiber or max . 3 / 4 ” AB / PVC insulation ( AS varies )
Max . 2 ” copper , or steel pipe with max . 1-1 / 2 ” glass fiber ( AS = 1 / 2 ” to 1 ”)
Max . 2 ” copper , or steel pipe with max . ¾ ” AB / PVC insulation ( AS = 3 / 8 ” to 1 ”)
Max . 4 ” copper , steel , or cast-iron pipe with ¾ ” AB / PVC insulation ( AS = 0 ” to 7 / 8 ”)
Max . 4 ” copper , steel , or cast-iron pipe with 1-1 / 2 ” glass fiber insulation ( AS = 0 ” to 7 / 8 ”)
Max 2 ” CPVC pipe ( c ) with 1 ” Glass fiber insulation ( AS = 1 / 8 ” to 1 ”)
Max 4 ” steel , cast iron , or copper with 1 ” glass fiber insulation ( AS = 0 ” to 1 / 2 ”)
MISCELLANEOUS MECHANICAL / DUCT PENETRATIONS IN WOOD-FRAMED FLOORS
Max . 4 ” ( 28 Ga ) diameter sheet metal duct w / o damper ( AS = 1 / 4 ” to ¾ ”)
Max . 10 ” ( 28Ga ) or 4 ” ( 30 Ga ) diameter sheet metal duct w / o damper ( AS = 0 ” to 1 ”)
Steel Grease or Air Duct with Firemaster DuctWrap by Thermal Ceramics
Steel strut , steel cable , steel rod , steel angle ( AS = 1 / 8 ” to 7 / 8 ”)
Max . 12 ” x 10 ” sheet metal duct ( AS = 0 ” to 1 ”)
Max . 7 ” diameter or max . 10 ” x 4 ” sheet metal duct with Firemaster DuctWrap by Thermal Ceramics
Max . 7 ” diameter or max . 10 ” x 4 ” sheet metal duct with Firemaster DuctWrap by Thermal Ceramics
Max . 7 ” diameter or max . 10 ” x 4 ” sheet metal duct with Fyrewrap DuctWrap by Unifrax
Max . 7 ” diameter sheet metal duct with Fyrewrap DuctWrap by Unifrax
Max . 7 ” diameter sheet metal duct with Firemaster DuctWrap by Thermal Ceramics
Wood-Framed Floors
System Number [ Similar FM Approved System ]
1 or 2 Hr ◼ FS-ONE MAX F-C-3012 1 Hr ◼ FS-ONE MAX F-C-3044 1 Hr ◼ CP 606 F-C-3071 1 Hr ◼ CP 606 F-C-3074 1 Hr ◼ FS-ONE MAX F-C-3094 1 Hr ◼ ◼ CFS-D 1 ” F-C-3110
1 or 2 Hr ◼ ◼ FS-ONE MAX F-C-5004
1 Hr ◼ FS-ONE MAX F-C-5036
1 or 2 Hr FS-ONE MAX F-C-5037
1 Hr CP 606 F-C-5065
1 Hr ◼ CP 606 F-C-5066
1 Hr ◼ FS-ONE MAX F-C-5086
1 or 2 Hr ◼ FS-ONE MAX F-C-5088
1 Hr FS-ONE MAX F-C-7013
1 Hr CP606 F-C-7025
1 or 2 Hr ◼ FS-ONE MAX F-C-7036
1 Hr
1 Hr
FS-ONE MAX CP 606
FS-ONE MAX CP 606
F-C-7042
F-C-7043
1 Hr ◼ FS-ONE MAX F-C-7055
1 Hr ◼
CFS-S SIL GG CFS-S SIL SL
F-C-7056
1 Hr ◼ FS-ONE MAX F-C-7057
1 Hr ◼ FS-ONE MAX F-C-7058
1 Hr ◼ FS-ONE MAX F-C-7059
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 40