Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
NON-METALLIC PIPES IN WOOD FRAMED FLOORS * ( CONTINUED )
Max . 4 ” ABS , PVC or CPVC ( c , v ) w / optional pipe coupling |
|
|
( AS = 0 ” to ½ ”) |
1 Hr |
◼ |
Max . 1-1 / 2 ” PVC or ABS plastic pipe and Tub Drain Fittings ( AS = 0 ” to 1 ”)
Max . 4 ” ABS or PVC toilet flange
Max . 2 ” FlowGuard Gold or Blazemaster CPVC ( c ) ( AS = 0 ” to 5 / 8 ”)
Multiple 1 ” PEX ( max qty 3 )
Max . 1 ” Polyethylene ( PEX ) SDR 9 Tubing ( c , v ) ( AS = 0 ’ to 7 / 8 ”) |
|
|
Max . 3 ” ABS , PVC , CPVC , or RNC ( c , v ) |
|
|
( AS = 3 / 16 ” to 5 / 16 ”) |
|
|
Max . 4 ” PVC or ABS w / branch line ( c , v ) |
|
|
( AS = 0 ” to ½ ”) |
|
|
Max . 3 ” ABS , PVC , CPVC ( c , v ), or 2 ” ENT |
|
|
( AS = 0 ” to 5 / 8 ”) |
|
|
Max . 4 ” PVC ( c , v ) against stud |
|
|
( AS = 1 / 16 ”) |
1 Hr |
◼ |
Max . 1 ” ENT ( one or more ) ( AS = 0 ” to 1 ”)
Max . 4 ” PVC or CPVC ( c , v ) ( AS = 1 / 16 ”)( collar on top of top plate )
Max . 1-1 / 2 ” ( 40mm ) PP ( SDR 11 ) Fusiotherm or Polystar CT-White ( c ) ( AS = 0 ” to 15 / 16 ”)
Max 1 / 2 ” Single Dura-line Microduct ( AS = min 0 ”)
Max . 2 ” Aquatherm Greenpipe PP-R ( SDR 7.4 or 11 ), Bluepipe PP-RCT ( SDR 9 or 11 or 17.6 ) Niron PP-RCT ( by Nupi Americas ( SDR 7.3 , 9 , 11 or 17 ), Aquatechnik PP-RCT ( SDR 7.4 , 11 or 17.6 ) and Uponor PP-RCT ( SDR 9 or 11 ), ( AS 0 ” to 1 ”)
Max . 6 ” PVC , CPVC ( SDR 13 . 5 ), PVC Conduit ( AS 0 ” to 1 / 2 ”)
Max . 4 ” PVC , CPVC ( SDR 13 . 5 ), PVC Conduit ( AS varies )
Max . 2 ” Aquatherm Greenpipe PP-R ( SDR 7.4 ), Niron PP-RCT ( by Nupi Americas ( SDR 7.3 ), Aquatechnik PP-RCT ( SDR 7.4 ), XFR-PVC ( c , v ) ( AS 0 ” to 1 ”) Canada only 50 Pa
Max . 4 ” Aquatherm Greenpipe PP-R ( SDR 7.4 or 11 ), Bluepipe PP-RCT ( SDR 9 or 11 ) Niron PP-RCT ( by Nupi Americas ( SDR 7.3 , 9 , or 11 ), Aquatechnik PP-RCT ( SDR 7.4 or 11 ) and Uponor PP-RCT ( SDR 9 or 11 ) ( AS 0 ” to 1-5 / 8 ”) Canada only 50 Pa
CP 648E / 1-3 / 4 ” w / Ret Collar or CP 643N
Wood-Framed Floors
System Number [ Similar FM Approved System ]
F-C-2232
1 Hr ◼ CP 606 F-C-2262
1 Hr ◼ CP 606 F-C-2263
1 Hr FS-ONE MAX F-C-2270
1 or 2 Hr ◼ FS-ONE MAX F-C-2310
1 Hr ◼ FS-ONE MAX F-C-2334
1 Hr CP648S F-C-2335
1 Hr ◼ CP 643N F-C-2382
1 Hr FS-ONE MAX F-C-2389
CP 648E / 1-3 / 4 ” w / Ret Collar ( U-shaped )
F-C-2401
1 Hr ◼ FS-ONE MAX F-C-2403
1 Hr CP 643N F-C-2404
1 Hr ◼ FS-ONE MAX F-C-2429
1 Hr ◼ ◼ CFS-D 1 ” F-C-2432
1 Hr ◼ FS-ONE MAX F-C-2508
1 Hr ◼ CP 643N F-C-2515
1 Hr ◼
CP 648E / 1-3 / 4 ” CP 648S
F-C-2516
1 Hr ◼ FS-ONE MAX F-C-2517
1 Hr ◼
FS-ONE MAX , CP 648E / 1-3 / 4 ” w / Ret Collar
F-C-2850
NEW Max . 1-1 / 2 ” PVC 2 Hr CP 643N FM 240 NEW Max . 2 ” PVC , Max . 1 ” cross linked polyethylene ( XLPE ) 1 Hr FS-ONE MAX FM 273
NEW
Max 4 ” PVC ( AS = 0 ” to 1 / 4 ”)
1 Hr CP 643N FM 274
NEW Max . 2 ” PVC , Max . 1 ” cross linked polyethylene ( XLPE ) 2 Hr FS-ONE MAX FM 275
NEW
NEW
NEW
Max 4 ” PVC ( AS = 0 ” to 1 / 4 ”)
Max . 3 ” ABS ( AS = 0 ” to 1 / 2 ”)
Max . 2 ” ABS ( AS = 0 ” to 15 / 16 ”)
2 Hr CP 643N FM 276
1 Hr ◼ FS-ONE MAX FM 686
1 or 2 Hr FS-ONE MAX FM 688
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 39