WOOD-FRAMED FLOORS
Hilti Firestop Selection Chart — U . S .
Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
BLANK OPENINGS IN WOOD-FRAMED FLOORS
Max . 2 ” dia blank opening
1 or 2 Hr ◼
METALLIC PENETRATIONS IN WOOD-FRAMED FLOORS
Max . 4 ” steel , cast iron , copper , conduit or EMT pipe ( AS = 0 ” to 1 ”) 1 or 2 Hr ◼ ◼
Max . 6 ” steel , cast iron , conduit , max . 4 ” EMT , or max . 2 ” flexible steel conduit ( AS = 1 / 4 ” to ¾ ”)
Max . 4 ” steel , cast iron , copper , conduit , or EMT ( AS = 0 ” to 7 / 8 ”)
Max . 4 ” cast iron toilet flange with fittings ( AS = 1 / 4 ”)
Max . 1-1 / 2 ” cast iron bathtub drain with PVC , ABS or brass waste / overflow fittings ( AS = 1 / 4 ”)
Max . 1 ” copper , steel , cast iron , steel conduit or EMT ( membrane penetration ) ( AS = 0 ” to 7 / 8 ”)
Max . 1 ” flexible steel conduit or gas piping ( mq = 3 ) ( AS = 0 ” to1-1 / 4 ”)
Max . 3 / 4 ” steel , cast iron , conduit or EMT pipe , or max 1 / 2 ” copper pipe ( AS = min . 0 ”)
FS-ONE MAX CP 606
FS-ONE MAX CP 606 CFS-S SIL GG
Wood-Framed Floors
System Number [ Similar FM Approved System ]
F-C-0002
F-C-1009
1 or 2 Hr FS-ONE MAX F-C-1059
1 Hr
1 Hr
1 Hr
CP 606 FS-ONE MAX
FS-ONE MAX CP 606
FS-ONE MAX CP 606
F-C-1106
F-C-1134
F-C-1135
1 Hr ◼ FS-ONE MAX F-C-1142
1Hr
◼
FS-ONE MAX CP 606
F-C-1147
1 Hr ◼ ◼ CFS-D 1 ” F-C-1168
NEW Max . 4 ” Copper ( AS = 0 ” to 1 / 2 ”) 1 Hr ◼ FS-ONE MAX FM 687
NON-METALLIC PIPES IN WOOD FRAMED FLOORS *
Max . 4 ” PVC or CPVC ( c , v ) ( AS = 0 ” to 1 / 2 ”)
Max . 4 ” PVC , CPVC , ABS or FRPP ( c , v ) ( AS = 0 ” to 1 / 2 ”)
Max . 2 ” PVC or CPVC ( c , v ) ( AS = 1 / 4 ” to 3 / 8 ”)
Max . 1 ” Polyethylene ( PEX ) SDR 9 Tubing ( c , v ) ( AS = 0 ” to 1 / 2 ”)
Max . 2 ” ABS , PVC or CPVC ( c , v ) ( AS = 0 ” to 5 / 8 ”)
Max . 2 ” ABS , PVC or CPVC ( c , v ) ( AS = 0 ” to 5 / 8 ”)
Max . 2 ” PVC or CPVC ( c , v ) ( AS = 1 / 2 ” to 1-1 / 8 ”)
Max . 2 ” ABS or PVC tub drain
Max . 4 ” ABS or PVC pipe with toilet flange ( AS = 0 ” to 1 / 2 ”)
Max . 1-1 / 2 ” PVC or ABS plastic pipe and Tub Drain Fittings
Max . 1-1 / 2 ” PVC or ABS plastic pipe and Tub Drain Fittings
Max . 1 ” PEX ( c , v ) ( AS = 1 / 4 ”)
Max . 2 ” PVC , CPVC or ABS ( c , v ) ( AS = 0 ” to ¼ ”)
2 Hr ◼
Ret . Collar w / FS-ONE MAX
F-C-2029
1 or 2 Hr ◼ CP 643N F-C-2030
1 or 2 Hr FS-ONE MAX F-C-2071
1 or 2 Hr ◼ FS-ONE MAX F-C-2081
1 or 2 Hr ◼ CP 643N F-C-2128
1 Hr ◼ FS-ONE MAX F-C-2142
1 or 2 Hr ◼ FS-ONE MAX F-C-2160
1 Hr ◼ CP 648E / 1 ” F-C-2189
1 Hr ◼ FS-ONE MAX F-C-2203
1 Hr FS-ONE MAX F-C-2204 1 Hr ◼ CP 648E / 1 ” F-C-2205
1 Hr CP 648E / 1 ” F-C-2230
1 Hr ◼
CP 648E / 1-3 / 4 ” w / Ret Collar
F-C-2231
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 38
Non-Metallic Pipes * ( continued ) ➜