Firestop Selection Chart | Página 21

Concrete Floors / Walls
CLICK CATEGORY INFO BELOW :
Penetrating Item ( s ) F-Rating T-Rating L-Rating W-Rating Product
System Number [ Similar FM Approved System ]
Blank Openings
Metallic Penetrants
NEW
NEW
NEW
NEW
INSULATED PIPES IN CONCRETE FLOOR / WALLS ( CONTINUED )
Max . 2 ” Steel or Copper pipe with 1 ” or 1-1 / 2 ” glass fiber insulation
Max . 1 ” Steel or Copper pipe with nominal 1-1 / 2 ” cellular glass ( Foamglass )
Nom . 6 ” or 8 ” Steel with Nom . 1 ” Glass Fiber Insulation , Nom . 6 ” or 8 ” Cast-Iron with Nom . 1 ” Glass Fiber Insulation , Nom . 6 ” or 8 ” Ductile Iron with Nom . 1 ” Glass Fiber Insulation
Nom . 6 ” or 8 ” Steel with Nom . 1 ” or 2 ” Glass Fiber Insulation , Nom . 6 ” or 8 ” Cast-Iron with Nom . 1 ” or 2 ” Glass Fiber Insulation , Nom . 6 ” or 8 ” Ductile Iron with Nom . 1 ” or 2 ” Glass Fiber Insulation Canada only
Multiple 3 ” copper , steel , cast iron ( mq = 5 ) with 1 ” glass fiber or ab / pve ( 6 ” concrete ) ( AS = ¼ ” to 6 ”)
Max . 4 ” steel , cast iron or copper with ¾ ” or 1 ” ABPVC / 1 ”, 1-1 / 2 ” or 2 ” of glass fiber ( 6 ” to 12 ” concrete )
Max . 2 ” steel or copper with ¾ ” or 1 ” ABPVC / 1 ”, 1-1 / 2 ” or 2 ” of glass fiber ( 6 ” to 12-1 / 2 ” hollow core )
Max . 8 ” steel , cast iron , or copper with 1 ” or 2 ” glass fiber ( 6 ” concrete )
Max . 2 ” PEX ( Uponor Aquapex or Wirsbo Hepex ) ( closed ) with Nom . 1 ” Glass Fiber through CFS-DID or HC ( hollow-core )
Max . 10 ” steel or max . 4 ” copper with 2 ” thick glass-fiber insulation ( AS = 1 ” to 1-1 / 8 ”)
Max . 12 ” steel or max . 6 ” copper pipe with 1-1 / 2 ” glass fiber insulation ( sleeved ) ( AS = 1-1 / 4 ” to 1-1 / 2 ”)
Max . 4 ” steel or max . 2 ” copper with ½ ” to 1 ” AB / PVC insulation ( AS = 0 ” to 1-1 / 2 ”)
Max . 12 ” steel or max 6 ” copper with 1 ”, 1-1 / 2 ” or 2 ” glass-fiber insulation ( AS = 0 ” to 1-1 / 2 ”)
Max . 10 ” steel pipe with max . 3 ” thick glass-fiber insulation ( AS = 1 / 2 ” to ¾ ”)
Max . 10 ” steel , cast iron or 4 ” copper pipe with max . 3 ” thick glass-fiber insulation ( AS = 1 / 2 ” to ¾ ”)
Max . 1 ” copper with max . 3 / 4 ” thick AB / PVC insulation ( Shaft Wall ) ( AS = 1 / 4 ” to 1-1 / 8 ”)
Max . 1 ” copper with max . 2 ” thick glass-fiber insulation ( Shaft Wall ) ( AS = 1 / 4 ” to 1-1 / 8 ”)
Beverage line set . Multiple ½ ” dia PEX or PE Tubing with AB / PVC Insulation ( AS = 0 ” to 1 ”)
Max . 4 ” steel , cast iron or copper pipe w / 1 ” to 1-1 / 2 ” glass fiber ( AS = 0 ” to 7 / 8 ”)
Max . 4 ” steel , cast iron , 2 ” copper or ½ ” to ¾ ” AB / PVC ( AS = 0 ” to 7 / 8 ”)
Max . 12 ” steel or 6 ” copper with max . 2 ” glass fiber ( optional sleeve ) ( AS = 0 to ½ ” for steel , 0 ” to 1-7 / 8 ” for copper )
Max . 4 ” PVC or CPVC with 1-1 / 2 ” glass fiber or 1 ” AB / PVC ( AS = 0 ” to 1 ”)
Max . 1-1 / 2 ” CPVC ( c ) with 1 ” glass fiber ( AS = 1 / 4 ” to 7 / 8 ”)
Max . 2 ” CPVC ( c ) with 1 ” glass fiber or AB / PVC ( AS = 1 / 4 ” to 7 / 8 ”)
Max . 1 / 2 ” PEX with 3 / 4 ” AB / PVC ( AS = 1 / 4 ” to 7 / 8 ”)
Max . 6 ” steel or cast iron pipe 3 ” glass fiber ( AS = 1 / 4 ” to 1-3 / 4 ”)
Max . 4 ” PEX with 1-1 / 2 ” glass fiber ( AS = 0 ” to 1 / 8 ”)
2 or 3 Hr ◼ CFS-CID MD M , P , or PX F-A-5070
2 Hr ◼ CFS-CID MD P or PX F-A-5071
2 Hr ◼ CFS-CID MD 8 ”, 10 ” F-A-5076
2 Hr ◼ CFS-CID MD 8 ”, 10 ” F-A-5077
2 Hr
FS-ONE MAX CFS-S SIL GG CFS-S SIL SL
F-B-5003
3 Hr ◼ CFS-DID C F-B-5004
3 Hr ◼
CFS-DID C / HC8 / HC10 / HC12
F-B-5005
2 Hr ◼ CFS-CID P F-B-5009
2 Hr ◼ CFS-DID F-B-5010
2 Hr
Ret . Collar w / FS-ONE MAX
W-J-5003
4 Hr FS-ONE MAX W-J-5028
1 or 2 Hr ◼ FS-ONE MAX W-J-5041
1,2 or 3 Hr
◼ FS-ONE MAX W-J-5042
2 Hr CP 648E / 1-3 / 4 ” W-J-5057
2 Hr CP 648E / 1-3 / 4 ” W-J-5058
1 or 2 Hr FS-ONE MAX W-J-5066
1 Hr ◼ FS-ONE MAX W-J-5067
2 Hr
2 Hr ◼
2 Hr ◼
CP 648E / 1-3 / 4 ” w / Ret Collar
FS-ONE MAX CP 606 CP 601s CFS-S SIL GG
FS-ONE MAX CP 606
W-J-5122
W-J-5134
W-J-5136
1 or 2 Hr FS-ONE MAX W-J-5140
2 Hr ◼
CP 648E w / Ret Collar
W-J-5145
2 Hr ◼ FS-ONE MAX W-J-5151
2 Hr ◼
CP648E / 1-3 / 4 ” FS-ONE MAX
W-J-5152
2 Hr ◼ FS-ONE MAX W-J-5190
2 Hr ◼ FS-ONE MAX W-J-5191
2 Hr ◼ CP 648E W-J-5192
Non-Metallic Pipes *
Cables / Cable Trays
Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings
Metallic Penetrants
Non-Metallic Pipes *
Cables
Cable Trays
Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls
Concrete Floors / Walls
Max . 7 / 8 ” Streamline ACR-Type L Copper Tubing with Nom . 1 / 2 ” Polyethylene Insulation
2 Hr ◼
CP 648-E FS-ONE MAX
W-J-5193
20
Insulated Pipes ( continued ) ➜