Concrete Floors / Walls |
CLICK CATEGORY INFO BELOW : |
|||
Penetrating Item ( s ) F-Rating T-Rating L-Rating W-Rating Product |
System Number [ Similar FM Approved System ] |
Blank Openings
Metallic Penetrants
|
||
|
NEW
NEW
NEW
|
INSULATED PIPES IN CONCRETE FLOOR / WALLS ( CONTINUED )
Max . 10 ” steel or cast iron with 1 ” to 3 ” glass fiber ( AS = 1 / 2 ” to 2-1 / 8 ”)
Max . 4 ” steel , cast iron or copper with 1 ” to 2 ” glass fiber ( bottom side access ) ( AS = 1 / 2 ” to 1-1 / 2 ”)
Max . 4 ” steel , cast iron or Max . 2 ” copper with 1 ” to 2 ” glass fiber and optional steel sleeve ( 2-1 / 2 ” concrete ) ( AS = 1 / 4 ” to 1-1 / 8 ”)
Max . 2 ” ( 63mm ) PP ( SDR 11 ) Fusiotherm or Polystar CT-White ( c ) w / ½ ” to 1-1 / 2 ” thick glass fiber ( AS = 3 / 8 ” to 1-1 / 8 ”)
Max . 3 ” Cosmoplast PP-R or Coprax PP-R plastic pipe ( c ) with nominal 1 ” polyolefin or AB / PVC ( AS = 0 ” to 1 ”)
Nom . 12 ” Aquatherm Bluepipe MF PP-R ( SDR 9 or 11 ), Nom 12 ” Niron Multi Cima PP-RTC ( SDR 7.3 ) ( AS 1 / 2 ” to 1-1 / 8 ”)
Max . 20 ” steel pipe with max . 3 ” glass-fiber insulation ( 5-1 / 2 ” concrete ) ( AS = 1 ” to 2-1 / 4 ”)
Max . 4 ” steel or copper with max . 1 ” glass fiber insulation ( hollow core ) ( AS = 0 ” to 7 / 8 ”)
Max . 2 ” steel , cast iron , or copper with 1 ” glass fiber insulation ( bottom side access ) ( AS = 0 ” to 1-7 / 8 ”)
Max . 10 ” steel pipe with 2 ” glass fiber insulation ( AS = 1 / 4 ” to 1 / 2 ”)
Max . 4 ” steel or copper pipe with nominal ¾ ” AB / PVC insulation ( 2-1 / 2 ” concrete )
2 Hr
2 Hr
CP 648E / 1-3 / 4 ” FS-ONE MAX
CP 648E / 1-3 / 4 ” FS-ONE MAX
C-AJ-5341
C-AJ-5342
2 Hr ◼ FS-ONE MAX C-AJ-5343
2 Hr ◼ CP 648E / 1-3 / 4 ” C-AJ-5352
2 Hr ◼
CP 648E / 1-3 / 4 ” w / Ret Collar
C-AJ-5385
2 Hr ◼ CFS-BL C-AJ-5432
4 Hr FS-ONE MAX C-BJ-5006
2 Hr FS-ONE MAX C-BJ-5013
2 hr FS-ONE MAX C-BJ-5015
2 Hr
2 Hr
Max . 4 ” steel or copper pipe with max . 2 ” thickness glass-fiber insulation ( 2-1 / 2 ” concrete )
2 Hr
Max . 4 ” steel or copper pipe with max . 3 / 4 ” thickness AB / PVC insulation ( 2-1 / 2 ” concrete ) ( AS = 0 ” to 1-3 / 8 ”)
Max . 12 ” steel or max . 6 ” copper pipe with max . 1-1 / 2 ” thickness glass-fiber insulation ( optional sleeve ) ( 2-1 / 2 ” concrete ) ( AS = 1 / 2 ” to 1-7 / 8 ”)
Max . 3 ” copper , steel , or cast iron with max . 1 ” thick glass fiber or AB / PVC insulation ( max qty 3 ) ( AS = 1 / 4 ” to 2 ”)
Max . 1-1 / 2 ” copper , steel , or cast iron with 1 ” thick glass fiber or ¾ ” AB / PVC insulation ( max qty 5 ) ( 2-1 / 2 ” concrete floor ) ( AS ¼ ” or ½ ” to 2 ”) ( fan coil )
Max . 8 ” steel , cast iron or max . 4 ” copper with max . 1-1 / 2 ” glass fiber insulation ( AS for steel / iron = ½ ” to 2 ”, AS for copper = 1 / 4 ” to 2-5 / 8 ”)
Max . 4 ” steel , cast iron or copper with ¾ ” or 1 ” ABPVC / 1 ”, 1-1 / 2 ” or 2 ” of glass fiber ( 2-1 / 2 ” to 8 ” concrete )
Max . 8 ” steel , cast iron , 4 ” copper with 1 ” glass fiber ( AS = 1 / 4 ” to 5 / 8 ”)
Insulated Aquatherm Greenpipe PP-R through CFS- DID 6 ” MD ( 3 ” PP-R with 1 ” Glass Fiber or 2 ” PP-R with 2 ” Glass Fiber )
Max . 2 ” PEX ( Uponor Aquapex or Wirsbo Hepex ) ( closed ) with Nom . 1 ” Glass Fiber
Max . 2 ” steel pipe or copper pipe with nom . 1-1 / 2 ” thickness cellular glass ( foamglass ) insulation ( 4-1 / 2 ” concrete )
Max . 2 ” Steel or Copper pipe with 3 / 4 ” or 1 ” AB / PVC insulation
Ret . Collar w / FS-ONE MAX
CP 680-M CP 680-P CP 680-PX
CP 680-M CP 680-P CP 680-PX
CP 680-M CP 680-P CP 680-PX
CP 680-M CP 680-P CP 680-PX
F-A-5009
F-A-5015
F-A-5016
F-A-5017
F-A-5018
2 Hr FS-ONE MAX F-A-5019
2 Hr ◼ FS-ONE MAX F-A-5021
2 Hr
2 Hr
2 Hr ◼ ◼
CFS-S SIL GG CFS-S SIL SL
CFS-S SIL GG CFS-S SIL SL
CFS-S SIL GG CFS-S SIL SL
F-A-5032
F-A-5036
F-A-5042
3 Hr CFS-DID MD F-A-5046
3-Hr
◼
CFS-S SIL GG CFS-S SIL SL
F-A-5047
2 Hr ◼ CFS-DID F-A-5055
2 Hr ◼ CFS-DID F-A-5061
2 Hr ◼ CP 680-P F-A-5062
2 or 3 Hr ◼
CFS-CID MD M , P , or PX
F-A-5069
|
Non-Metallic Pipes *
Cables / Cable Trays
Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings
Metallic Penetrants
Non-Metallic Pipes *
Cables
Cable Trays
Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
|
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls |
|||||||||||||