Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 92

2. Any opening in such walls, whether or not such opening serves as an exit, shall be adequately protected against the passage of fire or smoke there from. 3. Swinging fire exit doors on horizontal exits shall swing with the exit travel. Where a horizontal exit serves on both sides of a wall there shall be adjacent openings with swinging doors at each wall, opening in opposite directions, with signs on each side of the wall or partitions indicating as the exit door which swings with the travel from that side, or other approved arrangements providing doors always swinging with any possible exit travel. 4. Sliding fire doors shall not be used on a horizontal exit except where the doorway is protected by a fire door on each side of the wall in which such sliding fire doors are located. In this case, one fire door shall be of the swinging type as provided in paragraph "C" (3) of this Section and the other may be an automatic sliding fire door that shall be kept open whenever the building is occupied. E. Omission of Fire Partition on Certain Floors 1. Where a fire partition is used to provide a horizontal exit in any storey of a building, such partition may be omitted in any lower storey under the following conditions: a. The open fire area storey from which the fire partition is omitted shall be separated from the storeys above by construction having at least a 2-hour resistance rating. b. Required exits from the storeys above the open fire area storey shall be separated there from by construction having a 2-hour fire resistance rating and shall discharge outside without travel through the open fire area storey. c. Vertical openings between the open fire area storey and the storeys above shall be enclosed with construction having a 2-hour fire resistance rating. Other details shall be in accordance with the applicable provisions of Section 10.2.5.2 of this IRR. 2. Where a fire partition is used to provide a horizontal exit for any storey below the discharge level, such partition may be omitted at the level of the discharge under the following conditions: a. The open fire area storey shall be separated from the storeys below by construction having at least a 2-hour fire resistance rating. b. Required exits from storeys below the open fire area storey shall be separated from the open fire area storey by construction having a 76