Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 91

C. Bridges and Balconies 1. Each bridge or balcony utilized in conjunction with horizontal exits shall comply with the structural requirements for outside stairs and shall have guards and handrails in general conformity with the requirements of Section 10.2.5.4 of this IRR for stairs and smokeproof enclosures. 2. Every bridge or balcony shall be at least as wide as the door leading to it and not less than one hundred twelve centimeters (112 cm) for new construction. 3. Every door leading to a bridge or balcony serving as a horizontal exit from a fire area, shall swing with exit travel out of the fire area. 4. Where the bridge of balcony serves as a horizontal exit in one direction, only the door from the bridge or balcony into the area of refuge shall swing in. 5. Where the bridge or balcony serve as a horizontal exit in both direction, doors shall be provided in pairs swinging in opposite directions, only the door swinging with the exit travel to be counted in determination of exit width, unless the bridge or balcony has sufficient floor area to accommodate the occupant load of either connected or fire area on the basis of three-tenths square meter (0.3 m 2 ) per person or in existing buildings by specific permission of the City/Municipal Fire Marshal having jurisdiction, in which case doors on both ends of the bridge or balcony may swing out from the buildings. 6. The bridge or balcony floor shall be level with the floor of the building. 7. Ramps shall be employed where there is a difference in level between connected buildings or floor areas. Steps may be used where the difference in elevation is greater than fifty three and one-third centimeters (53.34 cm). Ramps and stairs shall be in accordance with the sections of this Rule pertaining to ramps, stairs and outside stairs. 8. All wall openings, in both of the connected buildings or fire areas any part of which is within three meters (3 m) of any bridge or balcony as measured horizontally or below, shall be protected with fire doors or fixed metal-frame wired-glass windows, except where bridges have solid sides not less than one and eight-tenths meters (1.8 m) in height, such protection of wall openings may be omitted. D. Openings through Walls for Horizontal Exits 1. Walls connected by a horizontal exit between buildings shall be of non-combustible material having a two (2) hour fire resistance rating. They shall provide a separation continuous to the ground. 75