2-hour fire resistance rating and all discharge directly outside without travel through the open fire area storey. c. Vertical openings between the open fire area storey and the floors below shall be enclosed with the construction having a 2-hour fire resistance rating. Other details shall be in accordance with the applicable provisions of Section 10.2.5.2 of this IRR. SECTION 10.2.5.7 RAMPS A. Application A ramp shall be permitted as component in a means of egress when it conforms to the general requirements of Section 10.2.5.2 of this IRR and to the special requirements of this Section. B. Dimensional Criteria The following dimensional criteria shall apply to ramps: Table 5: DIMENSIONAL CRITERIA FOR NEW RAMPS Dimensional Criteria mm in Feature Minimum width clear of all obstructions, except projections not more than 4½ in. (114 mm) at or below handrail height on each side Maximum slope Maximum cross slope Maximum rise for a single ramp run 44 1120 1 in 12 1 in 48 760 30 C. Protective Enclosure 1. When a ramp inside a building is used as an exit or exit component, it shall be protected by separation from other parts of the building as specified in Section 10.2.5.2 "B" of this IRR. 2. Fixed wired glass panels in steel sash may be installed in such a separation in a building fully provided with approved, supervised sprinkler system. 3. There shall be no enclosed usable space under ramps in an exit enclosure nor shall the open space under such ramps be used for any purpose. D. Other Details 1. A ramp and the platforms and landings associated therewith shall be 77