Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 388

SECTION 10.4.10.2 OPERATION A. Welding, Cutting and Hotworks Operations 1. Welding, cutting and hotworks operations shall be in accordance with Rule 10, Chapter 4, Division 17 of this IRR. 2. Electric arc welding generators or transformers, electrical wiring for light, power, heat, and signal or control circuits, as well as electrically operated equipments, tools, portable appliances, and devices shall be in accordance the Philippine Electrical Code. B. Spray Painting And Undercoating 1. Spray application operations, and processes shall be confined to spray booths, spray rooms, or spray areas. There shall be no open flame devices or spark-producing electrical equipment or appliances within six and one-tenth meters (6.1 m) radial distance horizontally while such operations are conducted. 2. Undercoating materials shall be dry before starting the engine of the undercoated vehicle. 3. Where only a small portion of a vehicle is spray painted and no accumulations of paint residues are allowed to form, such occasional painting shall be permitted in an open area located not less than six and one-tenth meters (6.1 m) radial distance horizontally from all open flame devices or spark-producing electrical equipment or appliances. SECTION 10.4.10.3 PROTECTION AND MAINTENANCE A. Fire Protective System 1. Approved, supervised automatic sprinkler system shall be provided in repair garages in accordance with Section 10.2.6.5 of this IRR and under the following conditions: a. Repair garages more than one (1) storey in height or located beneath another occupancy wherein such repair garage exceeds an area of seventy hundred forty three square meters (743 m 2 ). b. One-storey repair garages exceeding an area of one thousand one hundred fifteen square meters (1,115 m 2 ). c. All below-grade floors of repair garages, the ceilings of which are less than sixty-one hundredths meter (0.61 m) above grade. 2. Approved portable fire extinguishers shall be provided in all repair garages conforming to the provisions of Section 10.2.6.7 of this IRR. 372