Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 386

upon all gangplanks and ladders from the deck, pier or land to the ship. The signs shall also include the name of the fumigant used; the fumigator’s name and his/her address and telephone number; and the date and time of operation. Notices shall be printed in red ink on white background. Letters in the headlines must be at least 2 inches (51 mm) in height. A warning shall state that the occupied premises must be vacated at least two (2) to three (3) hours before the operation begins and shall not be reentered until the danger signs are removed by the proper authorities. SECTION 10.4.9.6 VENTING AND CLEANUP At the end of the exposure period, fumigators shall safely and properly ventilate the premises and contents and properly dispose all fumigant containers, residues, debris and other materials used in the fumigation. SECTION 10.4.9.7 THERMAL INSECTICIDAL FOGGING LIQUIDS No thermal insecticidal fogging liquid with a flash point below thirty-eight degrees Celsius (38°C) shall be used. During operation, fog shall not be blasted directly against any combustible object or materials, e.g. Cartons, papers, curtains and, or within 3 meters, therefrom. SECTION 10.4.9.8 RESTRICTED FUMIGANTS Use of Carbon Disulfide (CS 2 ) and Hydrocyanic Acid (HCN) shall be used only in agricultural fumigations. DIVISION 10. REPAIR GARAGES SECTION 10.4.10.1 CONSTRUCTION A. Repair garages shall be built in accordance with the National Building Code, and the provisions of this Section. B. A repair garage shall not be located within or attached to a building or structure used for any purpose other than a repair garage unless separated by walls and floor or floor-ceiling assemblies having a fire resistance rating of not less than two (2) hours. C. Any single area occupied for salesrooms, showrooms, offices, or similar spaces shall be separated from vehicle repair or parking areas by walls and floor or floor-ceiling assemblies having a fire resistance rating of not less than two (2) hours. D. Ceiling assemblies shall be constructed in such a manner as to restrict the passage of smoke, vehicle exhaust gases, and odors from the repair or parking area to these spaces. 370