Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 351

D. A clearance of not less than seventy six centimeters (76 cm) shall be maintained from building walls and partitions, and not less than ninety centimeters (90 cm)from ceilings of roof structural members with a minimum of forty five centimeters (45 cm) from sprinklers. E. Ammonium nitrate storage shall be separated by a space of nine meters (9m) or by tight non-combustible partition from storage of organic chemicals, corrosive liquids, compressed gases, flammable and combus- tible materials, or other contaminating substance such as sulfur, coal, flour, and metallic powders such a zinc, copper, and magnesium where storage of such materials is permitted with ammonium nitrate. F. Quantities of ammonium or ammonium nitrate fertilizers having no organic coating, in the form of crystals, flakes, grains or pills including fertilizers, dynamic grade, nitrous oxide grade and technical grade ammonium nitrate and ammonium nitrate phosphate (containing 60% of ammonium nitrate by weight) or more than fifty (50) metric tons of total weight, shall be stored in well-ventilated building of fire-resistive or noncombustible construction, or in a building of other type of construction equipped with an approved automatic sprinkler system. G. In populated areas, quantities of two thousand five hundred (2,500) tons or more shall be stored in well-ventilated buildings of one-hour fire-resistive or non-combustible construction equipped with an approved automatic sprinkler system. No combustible material or ammonium nitrate sensitizing contaminants shall be stored in this building. H. Storage of ammonium nitrate, coated or mixed with organic anti-caking materials, except compounded blasting agent shall not be permitted in populated and congested areas. Outside such areas, quantities of five hundred (500) metric tons or less may be stored in well-ventilated buildings of fire-resistive or non-combustible construction equipped with an ap- proved automatic firefighting system. SECTION 10.3.4.4.8 HIGHLY TOXIC MATERIALS A. Highly toxic materials shall be segregated from other chemicals and combustible and flammable substances in a room or compartment separated from other areas by walls and floor and ceiling assemblies having a fire-resistive rating of not less than one (1) hour. B. The storage room shall be provided with adequate drainage facilities and natural or chemical ventilation to the outside atmosphere. C. Readily legible warning signs and placards as prescribed in this Rule shall be prominently placed in the transport, storage and processing area. 335