Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 350

D. Readily legible warning signs and placards as prescribed in Chapter 3 Division 2 of this Rule. Signs shall be prominently placed in the storage and processing areas. SECTION 10.3.4.4.6 NITROMETHANE A. A suitable isolated nitromethane. outdoor storage are shall be provided for B. Hazardous processing shall not be permitted in the vicinity of this storage area. C. Nitromethane shall be stored in the drums in which it is received or in an underground tank with suitable corrosion protection and a minimum of sixty centimeters (60 cm) or earth over the tank or in barricaded tanks above-ground shall be provided. If the drum storage is not adequately protected by a fast-acting deluge automatic type fire-fighting system/the storage of nine hundred nine kilograms (909 kg.) or more shall be located at the following minimum distances from inhabited buildings. WEIGHT (Kilograms) Beginning of 908 kg 909 kg to 4546 kg 4547 kg to 9091 kg 9092 kg to 18,182 kg 18,183 kg to 36,364 kg APPROXIMATE NUMBER OF DRUMS 4 20 40 80 160 DISTANCE (meters) 30 60 90 120 150 D. Care shall be taken to avoid rough handling or contamination of this chemical. E. Readily legible warning signs and placards as prescribed in this Rule shall be prominently placed in the transport, storage and processing area. SECTION 10.3.4.4.7 AMMONIUM NITRATE A. All flooring in storage and handling areas shall be of non-combustible material and shall be without drains, traps, pits or pockets into which any molten ammonium nitrate could flow and be confined in case of fire. B. Each storage pile of bags or other authorized packages and container of such materials shall not exceed three hundred sixty five centimeters (365 cm) in height, three hundred sixty five (365 cm) centimeters in width and nine meters and fifteen centimeters (9.15 cm) in length. C. Pile units shall be separated by a clear space of not less than ninety two centimeters (92 cm) in width from the top of piles, serving as cross aisles in the storage are which shall not be less than one hundred twenty centime- ters (120 cm) in width. 334