Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 337

non-combustible or limited-combustible materials and that has at least one side predominantly open and a roof designed for ventilation and dispersal of escaped gas shall be considered located outdoors. ii. Compression, storage, and dispensing equipment located outdoors shall be: i.a. Above ground and not be beneath electric power lines, located at least three meters (3.0 m) from the nearest important building or line of adjoining property that a building can be built upon or from any source of ignition; i.b. More than three meters (3.0 m) from the nearest public street or sidewalk line and at least fifteen meters (15 m) from the nearest rail of any railroad main track; i.c. Provided with a clear space of at least one meter (1) m for access to all valves and fittings of multiple groups of containers; i.d. Provided with a minimum separation of three meters (3.0 m) from readily ignitable material of any stationary container; i.e. Provided with a minimum separation of six hundred ten centimeters (610 cm) between containers and aboveground tanks containing flammable or combustible liquids. iii. During outdoor fueling operations, the point where the fueling connection is made shall be located at least three meters (3.0 m) from any important building, mobile home, public sidewalk, highway, street, or road and at least one meter (1 m) from storage containers iv. A lesser distance shall be from buildings or walls constructed of concrete or masonry materials or of other material having a fire resistance rating of at least two (2) hours, but at least three meters (3.0 m) from any building openings. b. Indoors i. Compression, dispensing equipment, and storage containers connected for use shall be permitted to be located inside of buildings reserved exclusively for these purposes or in rooms within or attached to buildings in accordance hereof. 321