Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 338

ii. Storage shall be limited to not more than two hundred eighty three cubic meters (283 m 3 ) of natural gas in each building or room. Exception: containers. CNG stored in vehicle-mounted fuel supply iii. Deflagration (explosion) venting shall be provided in exterior walls or roof only. iv. Rooms within or attached to other buildings shall be constructed of non-combustible or limited-combustible materials. Interior walls or partitions shall be continuous from floor to ceiling, shall be securely anchored, and shall have a fire resistance rating of at least two (2) hours. At least one wall shall be an exterior wall. v. Indoor locations shall be ventilated utilizing air supply inlets and exhaust outlets arranged to provide uniform air movement to the extent practical. Inlets shall be uniformly arranged on exterior walls near floor level. Outlets shall be located at the high point of the room in exterior walls or the roof. A ventilation system for a room within or attached to another building shall be separate from any ventilation system for the other building. vi. Ventilation shall be by a continuous mechanical ventilation system or by a mechanical ventilation system activated by a continuously monitoring natural gas detection system where a gas concentration of not more than one-fifth (1/5) of the lower flammable limit is present. The ventilation rate shall be at least 1 m3/minĀ·12 m3 of room volume. In either case, the system shall shut down the fueling system in the event of failure of the ventilation system. Reactivation of the fueling system shall be by manual restart and shall be conducted by trained personnel. vii. Where installed, a gas detection system shall be equipped to sound an alarm and visually indicate when a maximum of one- fifth (1/5) of the lower flammable limit is reached. viii. Buildings and rooms used for compression, storage, and dispensing shall be classified in accordance with Table 28. No electrical sources of ignition, other than electrical installations as permitted by the preceding provision, shall be permitted. ix. Pressure relief devices on storage systems shall have pressure relief device channels to convey escaping gas to the outdoors and then upward to a safe area to prevent impinging on 322