Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 336

Exception: If both labels are located in one of the above areas, the labels shall be permitted to be combined into a single label. iv. Each vehicle shall be identified with a weather-resistant, diamond-shaped label located on an exterior vertical surface or near-vertical surface on the lower right rear of the vehicle (e.g., on the trunk lid of a vehicle so equipped, but not on the bumper of any vehicle) inboard from any other markings. The label shall be a minimum of one hundred twenty milimeters (120 mm) in length and eighty-three (83 mm) in height. The marking shall consist of a border and the letters “CNG”, twenty five millimetres (25 mm) minimum height centered in the diamond, of silver or white reflective luminous material on a blue background. C. CNG Compression, Storage, and Dispensing Systems 1. Compression equipment shall be designed for use with CNG and for the pressures and temperatures to which it can be subjected under normal operating conditions. It shall have pressure relief devices that limit each stage pressure to the maximum allowable service pressure for the compression cylinder and piping associated with that stage of compression. Compression equipment shall incorporate a means to minimize liquid carryover to the storage system. 2. Unattended CNG compression equipment shall be equipped with a high discharge and a low suction pressure automatic shutdown control. 3. Engine-driven compressor installations shall conform, where applicable, to NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines. 4. Control devices shall be installed so that internal or external icing or hydrate formation does not cause vehicle or fueling station malfunction. 5. The fueling connection shall prevent the escape of gas where the connector is not properly engaged or becomes separated. Fueling nozzles shall be listed in accordance with ANSI/IAS NGV1, Standard for Compressed Natural Gas Vehicle (NGV) Fueling Connection Devices. 6. Locations a. Outdoors i. A facility in which CNG compression, storage, and dispensing equipment are sheltered by an enclosure that is constructed of 320