Doors shall be equipped with latching device. Cabinets shall be painted with an approved in tumescent type Fire 1 retardant paint. Cabinets shall be conspicuously labeled in red letters “FLAMMABLE LIQUIDS". o. Storage cabinets shall be located at least eight meters (8 m) away from any source of ignition. p. Inside storage and handling rooms shall be constructed to meet the required fire-resistive rating. An approved, supervised sprinkler system shall be installed: i. Opening to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least ten centimeters (10 cm) in height or the floor in the room shall be at least ten centimeters (10 cm) below the surrounding floors. . A permissible alternate to the sill or ramp is an open-grated trench inside the room. A downgraded flooring shall be provided for spillage which drains to a safe location or an open-grated trench. ii. The room shall be provided with approved self-closing fire doors. Where other portions of the building or other properties are exposed, windows shall be of fire rated construction and properly sealed to avoid the spread of vapor. Wood of at least two and fifty four hundredths centimeters (2.54 cm) nominal thickness may be used for shelving rack, dunnage scuff boards, floor overlay and similar installations. iii. Ventilation shall be designed to provide for a complete change of air within the room at least six (6) times per hour. Ventilation shall be installed in accordance with the provisions of NFPA Pamphlet No. 91, "Blower and Exhaust System." It shall be controlled by a switch located outside the door. The ventilation equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Class I flammable liquids are dispensed or used within the room. iv. Inside storage and handling rooms shall contain at least one aisle with a minimum width of one meter (1 m). Storage shall not be closer one meter (1 m) to ceiling, or sprinkler heads or other obstructions. v. Stacking of containers shall be in accordance to Table 18 above. 254