Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 268

iii. Educational, healthcare, and detention and correctional occupancies shall store flammable and combustible liquids up to a maximum of four liters (4ℓ). iv. Mercantile and industrial occupancies, where rooms or areas are accessible to the public, storage shall be limited to quantities needed for display and normal merchandising purposes which shall not exceed eighty one liters (81ℓ) per square meter of gross floor area. c. In rooms or areas not accessible to the public, storage shall be limited to two hundred twenty seven liters (227ℓ) of Class IA, four hundred fifty four liters (454 ℓ) of Class IB, six hundred eighty one liters (681 ℓ) of Class 1C, nine hundred eight liters (908 ℓ) of Class II, one thousand eight hundred ninety three liters (1,893 ℓ) of combustible liquids or any combination of flammable liquids totaling nine hundred eight liters (908 ℓ). d. Containers less than one hundred thirteen liters (113 ℓ) capacity shall not be stacked more than one meter (1 m) or two containers high, whichever is greater, unless on fixed shelving or otherwise satisfactorily secured. Containers more than one hundred thirteen liters (113 ℓ) shall not be stacked one upon the other. All containers shall be stored in an upright position. e. Shelving shall be in a stable construction, of sufficient depth and such arrangement that containers displayed thereon shall not be easily displaced. f. Leaking containers shall be secured immediately from any possible source of ignition and the contents of which shall be transferred to an approved container and placed to a safe location not accessible to the public. The spill shall be appropriately contained and collected for proper waste disposal. g. Dispensing of Class II or III liquids from a single container having a capacity of more than two hundred twenty seven liters (227 ℓ) may be permitted outside of storage and handling room using dispensing device and fire control measures. Both the dispensing container and any reserve containers shall be considered as contributing to the totals allowed capacity under para “A” (2) (e) above. h. No pile shall be closer than one meter (1 m) to the nearest beam, chord, girder or other obstruction, and shall be one meter (1 m) below sprinkler deflectors, or discharge orifices of water spray, or other overhead fire protection systems or other obstructions. 252