4. Elevator floor location and operation annunciator.
5. Sprinkler valve and water flow display panels.
6. Emergency generator supervision devices, manual start and transfer
features. Emergency power must be available within ten (10) seconds
to operate the following:
a.
b.
c.
d.
e.
f.
g.
Emergency voice/alarm communication systems.
Fire alarm systems.
Automatic fire detection systems.
Elevator car lighting.
Escape route lighting.
Exit sign illumination.
Stairway doors
7. Controls for unlocking stairway doors simultaneously.
8. Telephone for fire department use with controlled access to the public
telephone system.
9. Fire pump status indicators.
10. Status indicators and controls for air handling systems.
11. The fire fighters control panel for smoke control systems.
12. Emergency power and standby power status indicators.
13. Schematic building plans indicating the typical floor plan and
detailing the building core, means of egress, fire protection systems,
firefighting equipment and fire department access.
14. Public address system, where specifically required by other rules of this
code.
B. Shut off valves and water flow devices at the riser connection must be
provided on each floor. Combined sprinkler/standpipe systems must have
an individual control valve and check valve at each sprinkler connection.
SECTION 10.2.19.6
STAIRWELLS
A. All stairwells shall be enclosed and protected in accordance with Rule 3.
All doors on stairwells shall be kept closed. Stairway doors, which can be
locked, must be provided with automatic electrical unlocking from the fire
command center.
B. All interior stairwells used as a means of egress shall be pressurized. In no
222