Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 237

topmost storey and the ground level is fifteen meters (15 m) or more. Building height shall be measured from the lowest level of fire department vehicle access to the floor of the highest occupiable storey. SECTION 10.2.19.3 SMOKE CONTROL High rise buildings shall be designed in such a manner that the levels of smoke concentration in protected spaces can be maintained within values that can be tolerated by occupants. The protected spaces shall include stairwells, at least one elevator shaft, and floor spaces readily accessible to all occupants and large enough to accommodate them. In the spaces to which the requirement for control of smoke level applies, the atmosphere shall not include more than one (1%) percent by volume of the contaminated atmosphere emanating from the fire area. SECTION 10.2.19.4 SPRINKLER SYSTEMS PROTECTION High rise buildings shall be protected with approved, supervised sprinkler systems designed and installed in accordance with NFPA 13, Standard for Installation of Sprinkler Systems. The approved, supervised sprinkler systems must protect all floor spaces including every closet and concealed spaces and plenums of certain configuration and construction – particularly where combustible materials are located such as exposed electrical wiring, combustible duct work, and combustible sound/thermal insulation. The system shall be interconnected to a fire command center of the building. SECTION 10.2.19.5 FIRE COMMAND CENTER A. For buildings ten (10) storeys or more, a fire command center shall be provided in a location approved by the City/Municipal Fire Marshal having jurisdiction and shall contain the following features: 1. The emergency voice/alarm communication system unit must have the following features: a. Provide a predetermined message to the fire area where the alarm originated, actuated by a smoke detector, sprinkler head, water flow device, or manual fire alarm. The message must provide applicable information and directions to occupants. b. The fire department two-way communication system must operate between the fire command center and every elevator, elevator lobby, exit stairway, and exit access corridor. A telephone station or jack shall be provided in each fire pump room. 2. The fire department communication unit. 3. Fire detection and alarm system annunciator unit 221