Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 189

6. Access to and Arrangement of Exits a. Access to all required exits shall be in accordance with Section 10.2.5.2 of this IRR, shall be unobstructed, and shall not be veiled from open view by ornamentation, curtain, or other appurtenance. b. Means of egress shall be so arranged that, from every point in any open area or from any room door, exits will be accessible in at least two (2) different directions. c. Doors between guest rooms and corridors shall be self-closing. d. Common path of travel shall not exceed ten meters (10 m). e. Dead end corridors shall not exceed six meters (6 m). 7. Discharge from Exits a. At least half of the required number of units of exit from upper floors, exclusive of horizontal exits, shall load directly to the street or through a yard, court, or passageway with protected openings and separated from all parts of the interior of the buildings. b. A maximum of fifty percent (50%) of the exits may discharge through areas on the floor of exit discharge provided: i. Such exits discharge to a free and unobstructed way to the exterior of the building, which way is readily visible and identifiable from the point of discharge from the exit. ii. The floor of discharge into which the exit discharge is provided with automatic fire suppression system and any other portion of the level of discharge with access to the discharge area is provided with automatic fire suppression system or separated from it in accordance with the requirements for the enclosure of exit. (See Section 10.2.5.2 of this IRR), iii. The entire area on the floor of discharge is separated from areas below by construction having a minimum fire-resistance rating of two (2) hours. 8. Lighting and Signs a. Each public space, hallway, stairway, or other means of egress shall have illumination in accordance with Section 10.2.5.11 of this IRR. Access to exit shall be continuously illuminated at all times. Any hotel and dormitory shall have emergency lighting installed in individual guest rooms or guest suites, hallways, landings of stairways and other appropriate areas as determined by the C/MFM having jurisdiction. 173