b. Every exit access door from public hallways or from corridors on floors with sleeping accommodations shall have an illuminated sign in accordance with Section 10.2.5.12 of this IRR. Where exits are not visible in a hallway or corridor, illuminated directional signs shall be provided to indicate the direction of exit. C. Protection 1. Protection of Vertical Openings a. Every stairway, elevator shaft and other vertical openings shall be enclosed or protected in accordance with Section 10.2.6.2 of this IRR. b. Any required exit stair which is so located that it is necessary to pass through the lobby or other open space to reach the outside of the building shall be continuously enclosed down to the lobby level. c. No floor below the floor of exit discharge, used only for storage, heating requirements, or other than hotel occupancy open to guest or the public, shall have unprotected openings to floors used for hotel purposes. 2. Protection of Guest Rooms a. In any new hotel building every corridor shall be separated from guest rooms by partitions having at least a one (1) hour fire resistance rating. b. Each guest room shall be provided with a door having a fire protection rating at least twenty (20) minutes. c. Openings in corridor partitions other than door openings shall be prohibited. d. Doors that open directly onto exit access corridors shall be self- closing and self-latching. 3. Interior Finish Interior finish, in accordance with Section 10.2.6.3 of this IRR and subject to the limitations and modifications therein specified, shall be as follows: a. For new construction or new Interior Finish i. Exits – Class A or Class B; ii. Lobbies, corridors – Class A or Class B; 174