C. Other Automatic Extinguishing Equipment 1. In any occupancy where the character of the potential fuel fire is such that extinguishment or control of fire will be more effectively accomplished by a type of automatic extinguishing systems other than automatic sprinkler system such as but not limited to carbon dioxide, dry chemical, foam, or water spray, a standard extinguishing system of appropriate type shall be installed subject to the approval of the City/Municipal Fire Marshal having jurisdiction. 2. If the extinguishing system is installed in lieu of a required, supervised automatic sprinkler system, the activation of the extinguishing system shall activate the building fire alarm system, where provided. The activation of an extinguishing system that is not installed in lieu of a required, supervised automatic sprinkler system shall be indicated at the building fire alarm system, where provided. D. Manual Extinguishing Equipment 1. Any fire extinguisher provided shall be installed, inspected and maintained in accordance with Section 10.2.6.7 of this IRR. 2. Each standpipe and hose system provided shall be in accordance with Section 10.2.6.6 of this IRR SECTION 10.2.6.6 STANDPIPES A. The design, installation and maintenance of Standpipe Systems shall be in accordance with NFPA 14, Standard for the Installation of Standpipe, Private Hydrant and Hose Systems. B. Classes of Standpipe System 1. A standpipe system shall be any of the following: a. Class I System. This system is provided with 64 mm (2 ½ in.) hose connections for full-scale firefighting at the following designated building locations: i. At each intermediate landing between floor levels in every required exit stairway; ii. On each side of the wall adjacent to the exit openings of horizontal exits; iii. In each exit passageway at the entrance from the building areas into the passageway; 100