Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 117

iv. In covered mall buildings, at the entrance to each exit passageway or exit corridor, and at exterior public entrances to the mall; v. At the highest landing of stairways with stairway access to a roof and on the roof where stairways do not access the roof. An additional 64 mm (2 ½ in) hose connection shall be provided at the hydraulically most remote riser to facilitate testing of the system; vi. Where the most remote portion of a nonsprinklered floor or storey is located in excess of 40 meters of travel distance from a required exit containing or adjacent to a hose connection, or the most remote portion of a sprinklered floor or storey is located in excess of 61 meters of travel distance from a required exit containing or adjacent to a hose connection, additional hose connections shall be provided, in approved locations, where required by the BFP. b. Class II System. This a hose connection provided with 38 mm (1 ½ in.) hose or within thirty seven meters (37 m) of a hose connection system shall be provided with 38 mm (1 ½ in.) hose connections for first aid fire fighting, so that all portions of each floor level of the building are within forty meters (40 m) of provided with less 38 mm (1 ½ in.) hose. Distances shall be measured along a path of travel originating at the hose connection. c. Class III System. This system shall be provided with connections as required for both Class I and Class II system hose C. Dry Standpipes 1. Dry standpipes shall be used for Class I system. 2. All buildings with required enclosed stairway or smokeproof enclosure shall have at least one dry standpipe outlet connection located at every floor level landing above the first floor of every required enclosure. No point within a building, requiring dry standpipes, shall be more than forty meters (40 m) travel distance from a dry standpoint outlet connection. 3. Dry standpipes shall not be concealed in building walls or built into pilasters. Portions of dry standpipes systems not located within an enclosed stairway or smokeproof enclosure shall be protected by a degree of fire resistance equal to that required for vertical enclosures in the building in which they are located. 101