Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 115

SECTION 10.2.6.5 AUTOMATIC EQUIPMENT SPRINKLERS AND OTHER EXTINGUISHING A. General 1. Automatic sprinklers if required by Division 8 through Division 17 of this Chapter shall be in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems 2. All automatic sprinkler and standpipe systems required by this code shall be inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water- Based Fire Protection Systems. Records of conducted maintenance and testing should be maintained and submitted together with FALAR 3. 3. Where a required automatic sprinkler system is out of service for more than 4 hours in a 24-hour period, the owner shall notify the nearest fire station immediately upon discovery but not later than 24 hours and a fire watch shall be assigned until the sprinkler system has been returned to service. 4. Sprinkler impairment procedures shall comply with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. B. Supervision 1. Supervisory Signals Where supervised automatic sprinkler systems are required by another Section of this Code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Monitoring shall include, but shall not be limited to, monitoring of control valves, fire pump power supplies and running conditions, water tank levels and temperatures, tank pressure, and air pressure on dry-pipe valves. Supervisory signals shall sound and shall be displayed either at a location within the protected building that is constantly attended by qualified personnel or at an approved, remotely located receiving facility. 2. Alarm Signal Transmission Where supervision of automatic sprinkler systems is required, waterflow alarms shall be transmitted to an approved, proprietary alarm receiving facility, a remote station, a central station, or the fire station. 99