INCORPORATING COLD CHAIN |
PROJECT |
|||||
|
engineering specifications provided by
GEA. The vessel skids were preassembled
at GEA’ s Cape Town workshop and
delivered to site as integrated units.
The accumulator is a GEA Slot
Separator, an in-house design incorporating
liquid separation, impingement and oil
drainage features for effective refrigerant
management and oil removal.
Witt GP ammonia pumps were selected
because the customer was already
familiar with Witt open-type ammonia
pumps, aligning the new installation
with its existing operational experience
and maintenance practices. Liquid-level
control is provided by a level transmitter
interfaced with a Danfoss ICAD actuator,
with a Danfoss ICS valve and regulating
pilot valve installed as a backup to
maintain reliable system operation.
LIQUID SUB-COOLING
To sub-cool the high-pressure liquid
ammonia, a plate-pack heat exchanger
was installed between the evaporative
condensers and the accumulator vessel
make-up station. Preliminary data captured
by the GEA Omni monitoring platform
indicates that an average sub-cooling of
approximately 5K is being achieved. This
reduces flash gas and improves system
efficiency.
The installation of a liquid sub-cooler
has become standard practice on new GEA
refrigeration installations because of its
proven energy saving benefits. Payback
calculations typically indicate a return on
investment within less than one year.
SEPARATING THE ELECTRICAL SYSTEMS FROM THE AMMONIA PLANT
Historically, electrical assemblies and plant
control equipment were installed within
the ammonia machine room. However,
with the introduction of VFDs, soft
starters, and increasingly sophisticated
control systems, best practice is to install
these devices in a clean, temperaturecontrolled
environment to ensure optimal
performance and reliability.
For these reasons, the electrical
switchgear, motor control centres, VFDs
and plant control systems were installed
in a dedicated electrical room separate
from the ammonia machine room.
|
This arrangement provides improved
environmental protection, facilitates
maintenance activities and enhances the
overall reliability of the refrigeration plant
control system.
The glycol cooling system for the
electrical room was integrated into the
ammonia refrigeration plant to provide
a reliable and energy-efficient means of
temperature control. An Alfa Laval heat
exchanger and inline pump were installed
in the plant room to supply chilled glycol
to an evaporator coil located within the
electrical room.
The evaporator coil is a commercial-type
unit supplied by HC Heat Exchangers. The
cooling arrangement is simple and robust,
with the associated switchgear integrated
into the electrical assembly.
REFRIGERATION FOR 24 CA STORES
The initial installation comprised the supply
and installation of refrigeration equipment
for 24 off 1 200-bin controlled atmosphere
stores. The selection of evaporators is one
of the most critical aspects of CA store
design. The evaporator coil assemblies
for the project were manufactured by HC
Heat Exchangers( HC Group) in accordance
with engineering guidelines and design
specifications provided by GEA.
From a performance perspective,
evaporators must be capable of delivering
sufficient capacity during the initial pulldown
phase while minimising dehydration
during the holding phase. Since pull-down
occurs only over a short period at the
beginning of the season, and the store
operates in a sealed, dormant state for
most of the year, this balance is essential.
For these reasons, blow-through
evaporators are typically preferred. During
holding, when fruit respiration is minimal,
the control of moisture loss becomes
critical. In blow-through configurations,
the air leaving the evaporator is more
saturated compared with draw-through
designs, resulting in reduced dehydration
of stored produce.
Fan energy consumption is also an
important consideration, as fan loads
can account for up to 40 % of the holding
load. This further reinforces the need for
optimised evaporator selection to ensure
|
both product quality and energy efficiency
over the full storage cycle.
The evaporator fans were supplied by
ebm-papst South Africa. After optimizing
the evaporator and stack pressure drops,
the fan selections were optimised to ensure
the most efficient and suitable solution for
the application. Inlet cones were fitted to
the evaporator fans to improve efficiency.
This simple addition allowed a reduction of
the fan motors by 1 size.
Each CA store is equipped with a
dedicated local control panel located
adjacent to the control valve assembly on
the mezzanine floor. Precise and stable
temperature control is critical to maintaining
optimal storage conditions within the
controlled atmosphere environment.
To maintain a simple and robust control
philosophy, each CA store is controlled
independently by Danfoss EKE 400
controllers. This approach is consistent
with the customer’ s existing CA store
installation, ensuring operational familiarity
and standardisation across both facilities.
The CA store controls also required
integration with the Gas-At-Site controlled
atmosphere equipment. Provision was
made for 24-volt DC relays in the GEA
control panels to enable the necessary
handshakes between the GasWatch system
and the CA stores.
MATCHING COMPRESSOR CAPACITY TO ACTUAL DEMAND
The Omni system was expanded to
also monitor the CA stores. The system
continuously monitors the air temperature,
suction saturated pressure and suction
valve position of each of the 24 stores.
Using this real-time data, the refrigeration
load of each CA store is calculated.
There are significant variations in
refrigeration demand throughout the
year. During the peak harvest season,
when the CA stores are being loaded
with product, refrigeration loads are at
their highest. In contrast, during midwinter
, when all 24 stores are in hold, the
refrigeration load is substantially reduced.
This created an opportunity to optimise
system performance by adjusting
|
compressor capacity to match the actual
cooling demand.
|
Controlled atmosphere at Sunnyside Gas At Site supplied the controlled atmosphere plant and controls for Betko Fresh Produce’ s Sunnyside facility, continuing a technical relationship spanning more than 30 years.
Once fruit is cooled, controlled atmosphere slows respiration and ripening by reducing oxygen and managing carbon dioxide in the storage room, helping preserve quality and extend storage life. Generating the required room atmosphere is the straightforward part. Two Isolcell PSA nitrogen generators – 200m ³/ h combined, on Kaeser compressed air – displace oxygen from a sealed room far faster than the fruit could consume it. Days saved establishing the atmosphere at the start of the season are storage life kept, rather than spent.
Holding 24 rooms at their required low-oxygen setpoints is the harder problem. Sealed fruit continuously respires: oxygen keeps falling, carbon dioxide keeps rising, and for optimal fruit quality both must stay inside a defined window. Four Isolcell ECO850 carbonadsorption scrubbers continuously remove CO₂ to hold it within that window.
Doing that in 24 rooms at once is a control problem. GasWatch, Gas At Site’ s proprietary control and monitoring system, measures and corrects the atmosphere in each room individually, integrated on the facility’ s Ignition SCADA platform and interfaced directly with the refrigeration controls, so atmosphere and temperature are managed as one system rather than two.
The complex is also DCA-ready, allowing fruit-response monitoring and the oxygen setpoint to be dictated by the fruit rather than a fixed protocol.
One of two Isolcell PSA nitrogen generators supplied by Gas At Site. Combined capacity is 200m ³/ h.
Supplied by Gas At Site( Pty) Ltd
|