Daytime exterior view of Betko ' s Sunnyside facility, showing the CA store, rooftop refrigeration equipment, storage tanks, and a forklift moving fruit bins at the loading bay.
Inside the plant room at Betko ' s Sunnyside facility, showing one of the Grasso V-Series ammonia compressor packages in the foreground, alongside a yellow air receiver and insulated pipework leading to pressure vessels further back.
Compressor capacity is controlled based on the saturated suction pressure measured at the accumulator vessel in the plant room. Operating the compressors at a higher suction pressure during periods of reduced load improves compressor efficiency and increases the coefficient of performance( COP).
The dynamic setpoint function within the Omni control system automatically adjusts the compressor suction pressure setpoint between-9 ° C and-4 ° C according to the cooling load of the CA stores. This results in a COP increase of at least 20 %. These adjustments are made incrementally every 60 seconds while continuously monitoring room temperatures to ensure that the required storage conditions are maintained. The GEA OmniHistorian stores years of operating information at a user-defined sampling rate.
A TEST ROOM FOR GATHERING DATA
CA Store 1 was selected as the designated test room. In addition to the sensors installed in the other stores, several additional sensors were installed in CA Store 1. These included relative humidity sensors, air pressure sensors, fruit spikes, as well as temperature sensors positioned beneath the floor and within the roof void.
The sensors installed inside the CA store are used to monitor and verify the differences in air pressure and relative humidity between the front and rear sections of the store. This additional instrumentation provides more detailed data for evaluating storage conditions.
Temperature sensors installed beneath the floor were placed in the earth to measure ground temperatures and estimate the transmission heat loads through the floor slab
Temperature sensors installed in the roof void recorded temperatures of up to 50 ° C during summer days, decreasing to approximately 22 ° C during the night. These measurements highlighted the significant temperature fluctuations experienced above the ceiling and demonstrated the importance of both the quality and thickness of the ceiling insulation.
The results confirmed that, over the large surface area of a CA store, effective ceiling and floor insulation is critical in reducing transmission heat gains and losses.
Based on recommendations and high-level payback calculations, the