PROJECT
INCORPORATING COLD CHAIN
Supplied by GEA
To accommodate these large capacity swings, the compressors are equipped with Variable Frequency Drives( VFDs), enabling precise capacity control and improved partload performance. For the initial installation, three Grasso V1100 compressors, each with an installed capacity of 581kW at-9 ° C suction and 33 ° C condensing conditions, were installed.
Unlike conventional fixedspeed compressors, reciprocating compressors on VSD compressors become increasingly more efficient when operating at reduced speeds. The Grasso V-series compressors offers the widest speed range on the market allowing the customer to get the maximum efficiency benefit and allowing the refrigeration plant to closely match cooling demand. This results in lower operating costs, improved system efficiency and enhanced overall plant performance throughout the year.
The Omni’ s Smart Sequencer automatically prioritises the compressors with the best part-load performance, ensuring high energy efficiency. Variable speed driven compressors can be grouped and speed synchronised, reducing energy consumption and extending the lifetime of the equipment.
Front elevation of the plant room at Betko ' s Sunnyside facility, with BAC evaporative condensers and red-piped ammonia lines mounted on the rooftop above the roller-door bays.
The Omni control system also includes a weather station to monitor actual ambient conditions at the plant room, including dry-bulb temperature and relative humidity. This data is used, among other functions, to verify prevailing wet-bulb conditions and enable floating head pressure control.
EVAPORATIVE CONDENSERS AND A LESSON FROM THE WATER SUPPLY
Betko currently operates BAC evaporative condensers at its Villiersdorp facility. To ensure consistency in equipment selection and provide reliable local service support, BAC ECI evaporative condensers with stainless-steel coils were specified for the new installation.
Standard practice is to control the condenser fans using Variable Speed Drives( VSDs). All fans are controlled simultaneously, increasing and decreasing speed together to improve system efficiency, minimise pressure fluctuations and reduce wear and tear on the fan motors.
One of the operational challenges encountered on site was the frequent interruption of the water supply to the plant room. As the facility is located on an operating farm, water outages occurred periodically and were often not immediately detected by operators. In several instances, the refrigeration plant continued operating until it eventually tripped on high discharge pressure because of the lack of condenser water supply.
To provide an early warning of water supply failures, a pressure sensor was installed on the water supply line feeding the evaporative condensers. The sensor was integrated into the GEA Omni control system, enabling real-time monitoring and alarm generation whenever the water pressure dropped below a preset value.
PRESSURE VESSELS AND REFRIGERANT MANAGEMENT
The ammonia pressure vessels were manufactured by VIOLA South Africa to
18