207 |
Play
SHR 14105R
Commercial Heat Recovery Ventilators
The SHR 14105R Commercial Heat Recovery Ventilation system (HRV)
complements today's tight buildings. Fantech Heat Recovery Ventilators (HRV)
are designed to supply air into a building while exhausting an equal amount of
contaminated air to the outside. The aluminum heat exchange core transfers
sensible energy between air steams resulting in tempering of the supply air and
reduced loads on the HVAC system.
During the defrost sequence, a motorized damper temporarily blocks the
incoming fresh air stream so that the warm air from the building can circulate
through the HRV. The exhaust blower shuts down and the supply blower
switches into high speed to maximize the effectiveness of the defrost strategy.
Airflow up to 1430 cfm @ 0.4” Ps
Push-push configuration
External low voltage contacts
Dual service doors & reversible electrical box
External three position switch (Low/Standby/Medium)
Improved BMS integration
•
•
•
•
•
•
Maximum continuous airflow
in.wg
cfm
0.3” Ps
0.4” Ps
0.5” Ps
0.6” Ps
0.7” Ps
0.8” Ps
0.9” Ps
1.0” Ps
1.1” Ps
1.2” Ps
1.3” Ps
1.4” Ps
1.5” Ps
Supply air flow (high)
1485
1430
1374
1319
1263
1207
1152
1096
1041
985
930
874
819
Exhaust air flow (high)
1485
1430
1374
1319
1263
1207
1152
1096
1041
985
930
874
819
Energy performance
Supply temperature
Net airflow
Apparent sensible effectiveness
F
cfm
%
35
1410
55
35
1058
63
95
1410
44
95
1058
47
Heating
O
Heating
Cooling
Specification data
Model
Voltage /
phase
V/~
W
A
cfm
SHR 14105R
120 / 1
1272
10.6
1430
fantech
Rated
power
Max
amps
Average airflow @
0.4” Ps
Connection
Defrost cycle
Shipping
weight
Side
Recirculation
325
Item #
lbs
List price
USD
40445-1
4,295.00