YORK_HVAC European catalogue_Mar. 2021_EN | Page 127

Outside Air or Mixing Supply Air Unit

YORK Modular Air Handling Units

Type 1
Outside Air or Mixing Supply Air Unit
FA damper RA damper
Cooling coil
G4 + F7 filters
Heating coil
Drain pan
Supply fan
For European Union countries heat recovery systems as per European Legislation EU / 1253 / 2014 should be implemented .
Model
Width B
Dimensions [ mm ]
Height H
Length L
Weight [ kg ]
Airflow range nominal m 3 / s m 3 / h
Power Input [ kW ]
YMA ( S11 ) 0970H-0950W 950 970 3 400 608 0.6 2 160 0.551 A + YMA ( S12 ) 0970H-1500W 1 500 970 3 400 810 1.2 4 320 1.054 A + YMA ( S13 ) 1570H-1550W 1 550 1 570 3 600 1 156 2.4 8 640 2.009 A + YMA ( S14 ) 1570H-2150W 2 150 1 570 3 800 1 483 3.6 12 960 2.948 A + YMA ( S15 ) 2250H-2150W 2 150 2 250 3 900 1 841 5.4 19 440 4.567 A + YMA ( S16 ) 2250H-2750W 2 750 2 250 4 100 2 269 7.2 25 920 5.962 A + YMA ( S17 ) 2860H-2850W 2 850 2 860 4 600 3 138 9.6 34 560 7.528 A + YMA ( S18 ) 2860H-3450W 3 450 2 860 4 200 3 329 12 43 200 9.72 A + YMA ( S19 ) 2860H-4050W 4 050 2 860 4 400 3 957 13.5 48 600 10.174 A +
Panel : Galvanised Steel 0.6mm - Frame : Aluminum PR55TT - Fire rated Rockwool insulation 100 kg / m3 density - Filter M6 / G4 + F7 - TT : T2 - TB : TB2 Casing Strength : D1 ( M ) - Casing Air Leakage + PA700 : L2 ( M ) - Casing Air Leakage -400Pa : L1 ( M )
EUROVENT Class 2016
AHU N ยบ 05.02.314 Range : YMA
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 127