YORK_HVAC European catalogue_Mar. 2021_EN | Page 126

NEW
Air Handling Systems and Terminal Devices | Air Handling Units

YMA Modular Air Handling Units

A complete range from 2,160 m ³/ h - 48,600 m ³/ h
NEW
Features
The YORK Modular Air Handling Units are available in 5 different configurations meeting the most common market requirements . The units with aluminum frame , galvanised steel panels and fire rated Rockwool insulation are all Eurovent A + certified .
All YORK Modular Air Handling Units meet following classifications :
• ErP conform
• Thermal Bridging Class : TB2
• Thermal Transmittance : T2
• Casing Strength : D1 ( M )
• Casing Air Leakage (+ 700Pa / -400Pa ): L2 ( M )/ L1 ( M )
Type 1 Type 2 Type 3 Type 4 Type 5
Indoor Air Quality Options
Ultraviolet Germicidal Irradiation : UV-C disinfection helps deactivate airborne infectious microorganisms like viruses and bacteria which can be disseminated through ventilation systems and that can cause the spread of infections . Effectiveness depends on the UVGI dosage , exposure time , and humidity level . Our selection software helps to make the right choice . It affects areas directly exposed to the light source . This includes the direct airstream and surfaces .
Mono-Polar Ionization or Electrostatic Precipitation : works by flooding the air with millions of either negatively or positively charged particles to react with both microbes and contaminants . This method is capable of capturing ≥ 0.01μm particles by the electrical charging of particles . The collector plates , which are oppositely charged , then capture these particles in the next step . It not only affects contaminants and microbes in the air , but also on surfaces , even hidden surfaces .
Bi-Polar Ionization : works by adding a controllable amount of both positive and negative oxygen ions to the supply air of the AHU . Oppositely charged ions attract to other particles , become bigger and heavier and can be trapped . In addition the positive and negative ions also surround surface proteins of VOC ’ s ( Volatile Organic Compounds ), bacteria , germs or virus and destroy it .
126 YORK Air-Conditioning Products