FIRESTOP APPLICATION SOLUTIONS
FIRESTOP APPLICATION SOLUTIONS
Firestop Product Selector
Application Type Product Type Fire Rating Approvals Additional Attributes |
Application Temperature Range |
Joints |
Penetrations |
Endo- Thermic |
Outlet Boxes |
Façade |
Steel Protection |
Wet-applied |
Dry-applied / Pre-formed |
1-Hr 2-Hr 3-Hr 4-Hr L-Rating W-Rating M-Rating T-Rating |
Movement( up to %) ASTM E1399 |
STC( up to) ASTM E90 |
Minimum |
Maximum |
FS ONE MAX Firestop Intumescent Sealant ■ ■ ■ ■ ■ ■ ■
UL 1479, UL 2079, ASTM E84, ASTM G21
■ ■ ■ ■ 7.50 % 62 35 ° F 104 ° F
CP 606 Firestop acrylic sealant ■ ■ ■ ■ ■ ■ ■
UL 1479, UL 2079, ASTM E2837, ASTM E84, ASTM G21
■ 19 %(+/-) 68 35 ° F 104 ° F
CP 605 Bottom-of-wall firestop sealant ■ ■ ■ ■ ■ ■ ■
ASTM C919, ASTM C834, ASTM E84, ASTM G21
■ N / A 64 35 ° F 104 ° F
CFS-S SIL GG Firestop Silicone Sealant ■ ■ ■ ■ ■ ■ ■
CFS-S
SIL SL Firestop Silicone Sealant ■ ■ ■ ■ ■ ■ ■ ■
UL 1479, UL 2079, ASTM C920, ASTM E84, ASTM G21
UL 1479, UL 2079, ASTM E 2307, ASTM E84, ASTM G21
■ ■ ■ 33 %(+/-) 59 35 ° F 104 ° F
■ ■ ■ 33 %(+/-) 59 35 ° F 104 ° F
CP
637 Firestop Mortar ■ ■ ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ N / A N / A 40 ° F 113 ° F
Firestop Sprays |
|
|
|
CFS-SP-WB Water-based Acrylic Sealant Spray |
■ ■ ■ ■ ■ ■ ■ ■ |
UL 1479, UL 2079, ASTM E2307, ASTM E2837, ASTM E1354, ASTM E84, ASTM G21 |
■ ■ 50 %(+/-) 59 39 ° F 104 ° F |
CFS-SP SIL Silicone-based Joint Spray ■ ■ ■ ■ ■ ■ ■
UL 2079, ASTM E2307, ASTM D6904, ASTM E84, ASTM G21
■ ■ 12.5 %(+/-) 59 35 ° F 104 ° F
CFP-SP
WB Fire Finish 120 + ■ ■ ■ ■ ■ ■ UL 263 / ASTM E119 N / A N / A 50 ° F 95 ° F
CFP-SP WB Fire Finish 60 + ■ ■ ■ ■ UL 263 / ASTM E119 N / A N / A 50 ° F 95 ° F
CFP-SP
AWHB All Weather High Build ■ ■ ■ ■ ■ ■ UL 263 / ASTM E119 N / A N / A 5 ° F 122 ° F
Firestop Foams
CP
620 Firestop Foam ■ ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ N / A N / A 50 ° F 86 ° F
CP 660 Flexible Firestop Foam ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ N / A N / A 50 ° F 95 ° F
Firestop Board
CFS-COS Firestop Composite Sheet ■ ■ ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ N / A 52(-22 F) 118 ° F
Firestop Blocks & Plugs
CFS-BL Firestop Block ■ ■ ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ ■ N / A 52 40 ° F 104 ° F
CFS- PL Firestop Plug ■ ■ ■ ■ ■ ■
UL 1479, ASTM E84, ASTM G21
■ ■ N / A 54 40 ° F 104 ° F
All products should be installed per an official UL listing. Check individual UL systems for specific fire ratings and / or additional attribute ratings per application.
Hilti, Inc.( U. S.) 1-800-879-8000 | en español 1-800-879-5000 www. hilti. com
DBS • 11 / 25