30RQS 039-160
Physical data
30RQS
Air conditioning application as per EN14511-3:2013
kW
Nominal cooling capacity
EER
kW/kW
Eurovent class, cooling
ESEER
kW/kW
Heating application as per EN14511-3:2013
kW
Nominal heating capacity
COP
kW/kW
Eurovent class, heating
Operating weight*
Standard unit without hydronic module
kg
Standard unit with hydronic module
Single high-pressure pump
kg
Dual high-pressure pump
kg
Compressors
Circuit A/B
Refrigerant*
Capacity control
Air heat exchangers
Fans
Quantity
Total air flow (at high speed)
l/s
Water heat exchanger
Hydronic module (option)
Dimensions
Length x depth x height
mm
039
045
050
060
070
078
080
090
100
120
140
160
38
2.84
C
3.80
43
2.70
C
3.77
50
2.65
D
3.81
59
2.77
C
3.61
64
2.70
C
3.61
74
2.58
D
3.57
78
2.79
C
3.84
86
2.70
C
3.77
96
2.70
C
3.88
113
2.69
D
4.04
132
2.77
C
3.75
149
2.58
D
3.67
42
3.08
B
47
3.05
B
53
3.03
B
61
3.03
B
70
3.06
B
78
2.87
C
80
3.08
B
93
3.02
B
101
3.09
B
117
3.06
B
138
3.07
B
158
2.97
C
506
513
539
552
553
560
748
895
903
959
1060
1078
1099
1136
1117
1127
2/2
2/2
2
10600
2
10600
535
543
569
582
582
590
778
927
935
995
561
569
594
608
608
616
804
972
980
1043
Hermetic scroll compressors, 48.3 r/s
2/2/2/2/2/2/2/3/3/3/R-410A
Pro-Dialog+
Grooved copper tubes and aluminium fins
Axial Flying Bird IV with rotating shroud
1
1
1
1
1
1
2
2
2
2
3800
3800
3800
5300
5300
5300
7600
7600
7600
7600
Direct expansion, plate heat exchanger
Single or dual pump, Victaulic screen filter, safety valve, expansion tank, purge valves (water and air), pressure sensors
1090 x 2109 x 1330
2273 x 2136 x 1330
NOTE: For the conditions please refer to page 73
*
Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate.
Electrical data
30RQS without hydronic module
039
045
050
060
070
078
080
090
100
120
140
Power circuit
Nominal power supply
V-ph-Hz 400-3-50 ± 10%
24 V via internal transformer
Control circuit supply
Maximum start-up current (Un)*
Standard unit
A
113.8
134.8
142.8
145.8
176.0
213.0
213.6
173.6
207.6
247.6
243.0
Unit with electronic starter option
A
74.7
86.5
93.8
96.2
114.4
139.8
139.8
kW
19.5
22.3
24.5
27.9
31.2
35.8
35.6
42.3
45.6
52.5
62.4
Maximum operating power input**
A
25.6
29.0
33.0
36.0
42.4
52.8
53.4
55.4
61.7
77.3
84.8
Nominal unit operating current draw***
*
Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
**
Power input, compressors and fans, at the unit operating limits (saturated suction temp. 10°C, saturated condensing temp. 65°C) and nominal voltage of 400 V (data given on the unit nameplate).
*** Standardised Eurovent condit