61AF 014-019
Physical data
61AF
014-7
Air conditioning application as per EN14511-3 : 2013
Condition 1
Nominal heating capacity
COP
Eurovent class, heating
Condition 2
Nominal heating capacity
COP
Operating weight*
Standard unit without hydronic module
Standard unit with hydronic module option
Compressor
Refrigerant*
Condenser
Fan
Quantity
Air flow
Evaporator
Dimensions
Length x depth x height
NOTE: For the conditions please refer to page 73.
*
014-9
019
kW
kW/kW
14.1
3.32
A
13.7
3.50
A
19.8
3.45
A
kW
kW/kW
13.9
3.89
13.5
4.16
20.2
4.24
kg
kg
159
169
One, hermetic scroll, 48.3 r/s
R-407C
Direct-expansion plate heat exchanger
Axial
2
2050
Grooved copper tubes and aluminium fins
159
169
206
216
2
2050
2
2000
1103 x 333 x 1278
1135 x 559 x 1579
l/s
mm
1103 x 333 x 1278
Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate.
Electrical data
61AF - Standard unit
Without pump
014-7
014-9
25
45
019
With pump
014-7
014-9
019
Power circuit
Nominal power supply
V-ph-Hz
230-1-50 ± 10%
400-3-50 ± 10%
400-3-50 ± 10%
230-1-50 ± 10%
400-3-50 ± 10%
400-3-50 ± 10%
24 V, via internal transformer
Control circuit supply
Maximum start-up current (Un)*
66
102
67
104
Standard unit
A
47
48
Unit with electronic starter option
A
0.82
0.82
0.82
0.82
0.82
0.82
Unit power factor at maximum capacity**
kW
6.41
5.90
8.80
6.41
6.10
9.20
Maximum unit power input**
A
22.9
7.9
12.4
23.7
7.9
12.4
Nominal unit current draw***
A
30.7
10.8
16.0
31.5
10.8
16.0
Maximum unit current draw (Un)****
*
Maximum instantaneous start-up current at operating limit values (maximum operating current of the pump + fan current + locked rotor current of the compressor).
** Power input, compressors and fan, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given on the unit nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature 40°C/45°C, outside air temperature 7°C.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
Operating range
70
Leaving water temperature, °C
65
60
55
50
45
40
35
30
25
20
-25 -20 -15 -10
-5
0
5
10
15 20
30
35 40
Entering air temperature, °C
Full load
81