Test Drive carrier katalog | Page 71
09TE/09FCTE
Physical data
Models
Fans/poles
Fan
arrangement
Single row
09-TE90 2MSB
09-TE90 3MSB
09-TE90 4MSB
09-TE90 5MSB
09-TE90 6MSB
09-TE90 7MSB
Double row
09-TE90 4MDB
09-TE90 6MDB
09-TE90 8MDB
09-TE90 10MDB
09-TE90 12MDB
09-TE90 14MDB
09-TE90 16MDB
6PH (Delta)
CAP
AF
kW
l/s
6PL (Star)
Lw/Lpa CAP
AF
dB(A) kW
l/s
8PH (Delta)
Lw/Lpa CAP
AF
dB(A) kW
l/s
8PL (Star)
Lw/Lpa CAP
AF
dB(A) kW
l/s
12PH (Delta)
Lw/Lpa CAP
AF
dB(A) kW
l/s
12PL (Star)
Lw/Lpa CAP
AF
dB(A) kW
l/s
Lw/Lpa
dB(A)
1 x 2 - ø900
1 x 3 - ø900
1 x 4 - ø900
1 x 5 - ø900
1 x 6 - ø900
1 x 7 - ø900
238
357
477
597
717
836
15483
23225
30967
38708
46450
54192
90/58
92/60
93/61
94/62
95/63
96/63
201
301
402
502
603
704
12083
18125
24167
30208
36250
42292
84/52
86/54
87/55
88/56
89/57
90/57
186
279
372
465
559
652
11194
16792
22389
27986
33583
39181
83/51
85/53
86/54
87/55
88/56
89/56
154
231
308
385
463
540
8561
12842
17122
21403
25683
29964
76/44
78/46
79/47
80/48
81/49
82/49
136
204
272
340
408
476
7189
10783
14378
17972
21567
25161
71/39
73/41
74/42
75/43
76/44
77/44
106
159
212
265
318
371
5236
7729
10306
12882
15458
18035
62/30
64/32
65/33
66/34
67/35
68/35
2 x 2 - ø900
2 x 2 - ø900
2 x 2 - ø900
2 x 3 - ø900
2 x 3 - ø900
2 x 3 - ø900
2 x 4 - ø900
399
599
800
1001
1201
1400
1602
27475
41213
54950
68688
82425
96163
109900
93/61
95/63
96/64
97/65
98/65
99/66
99/66
335
502
670
838
1006
1173
1341
21142
31713
42283
52854
63425
73996
84567
87/55
89/57
90/58
91/59
92/59
93/60
93/60
326
489
653
817
980
1145
1308
20375
30563
40750
50938
61125
71313
81500
86/54
88/56
89/57
90/58
91/58
92/59
92/59
258
387
517
646
776
905
1035
14686
22029
29372
36715
44058
51401
58744
79/47
81/49
82/50
83/51
84/51
85/52
85/52
227
341
455
569
684
798
912
12561
18842
25122
31403
37683
43964
50244
74/42
76/44
77/45
78/46
79/46
80/47
80/47
175
263
351
439
527
615
703
8753
13129
17506
21882
26258
30635
35011
65/33
67/35
68/36
69/37
70/37
71/38
71/38
CAP - Nominal capacity
AF - Air flow
Lw - Sound power level
Lpa - Sound pressure level at 10 m
Note: Performance data given for units with AC-motor fans, 400-3-50 power supply, refrigerant R-404A, Δt1 =15 K, operating pressure 26 bar, ENV327. For performance data for units with other refrigerants or
fans, and for 09FCTE 90 dry coolers, see technical documentation or electronic selection program.
Fan data
Correction factors for different refrigerants
Asynchronous Motors
Diameter
Speed*
Wiring
6P
900 mm
Number of poles
H
H
L
H
L
∆
∆
Y
∆
Y
8P
12P
Power input Full load
(kW)
current
(A)
2.2
5.3
1.3
3.5
0.8
1.7
0.5
1.5
0.25
0.65
Temperature difference ΔT, K
Refrigerant
8
10
12
0.67
0.80
R-404A – R-22 – R-134a – R-507 0.53
0.46
0.62
0.77
R-407C, R-407A
15
1.00
1.00
17
1.13
1.15
20
1.33
1.38
‘* H: High, L: Low
Diameter
910 mm
910 mm
Number of poles
NA
NA
Speed (rpm)
1000
910
750
690
560
610
560
470
330
200
Wiring
NA
NA
Power
input
(kW)
3.12
2.26
1.28
1.01
0.56
0.6
0.45
0.26
0.1
0.04
Full load
current
(A)
4.9
3.5
2.0
1.7
1.1
1.2
0.9
0.6
0.3
0.2
2209
EC-Motors
A
2200
Single-row models
Models
09TE 90 2MSB
09TE 90 3MSB
09TE 90 4MSB
09TE 90 5MSB
09TE 90 6MSB
09TE 90 7MSB
09TE 90 4MDB
09TE 90 6MDB
09TE 90 8MDB
09TE 90 10MDB
09TE 90 12MDB
09TE 90 14MDB
09TE 90 16MDB
Max. length A, mm
2465
3590
4715
5840
6965
8090
2465
3590
4715
5840
6965
8090
9215
Net weight, kg
469
691
872
1072
1273
1472
882
1301
1650
2018
2390
2785
3256
1636
Dimensions and weights
A
Double-row models
69
1200