Test Drive carrier katalog | Page 71

09TE/09FCTE Physical data Models Fans/poles Fan arrangement Single row 09-TE90 2MSB 09-TE90 3MSB 09-TE90 4MSB 09-TE90 5MSB 09-TE90 6MSB 09-TE90 7MSB Double row 09-TE90 4MDB 09-TE90 6MDB 09-TE90 8MDB 09-TE90 10MDB 09-TE90 12MDB 09-TE90 14MDB 09-TE90 16MDB 6PH (Delta) CAP AF kW l/s 6PL (Star) Lw/Lpa CAP AF dB(A) kW l/s 8PH (Delta) Lw/Lpa CAP AF dB(A) kW l/s 8PL (Star) Lw/Lpa CAP AF dB(A) kW l/s 12PH (Delta) Lw/Lpa CAP AF dB(A) kW l/s 12PL (Star) Lw/Lpa CAP AF dB(A) kW l/s Lw/Lpa dB(A) 1 x 2 - ø900 1 x 3 - ø900 1 x 4 - ø900 1 x 5 - ø900 1 x 6 - ø900 1 x 7 - ø900 238 357 477 597 717 836 15483 23225 30967 38708 46450 54192 90/58 92/60 93/61 94/62 95/63 96/63 201 301 402 502 603 704 12083 18125 24167 30208 36250 42292 84/52 86/54 87/55 88/56 89/57 90/57 186 279 372 465 559 652 11194 16792 22389 27986 33583 39181 83/51 85/53 86/54 87/55 88/56 89/56 154 231 308 385 463 540 8561 12842 17122 21403 25683 29964 76/44 78/46 79/47 80/48 81/49 82/49 136 204 272 340 408 476 7189 10783 14378 17972 21567 25161 71/39 73/41 74/42 75/43 76/44 77/44 106 159 212 265 318 371 5236 7729 10306 12882 15458 18035 62/30 64/32 65/33 66/34 67/35 68/35 2 x 2 - ø900 2 x 2 - ø900 2 x 2 - ø900 2 x 3 - ø900 2 x 3 - ø900 2 x 3 - ø900 2 x 4 - ø900 399 599 800 1001 1201 1400 1602 27475 41213 54950 68688 82425 96163 109900 93/61 95/63 96/64 97/65 98/65 99/66 99/66 335 502 670 838 1006 1173 1341 21142 31713 42283 52854 63425 73996 84567 87/55 89/57 90/58 91/59 92/59 93/60 93/60 326 489 653 817 980 1145 1308 20375 30563 40750 50938 61125 71313 81500 86/54 88/56 89/57 90/58 91/58 92/59 92/59 258 387 517 646 776 905 1035 14686 22029 29372 36715 44058 51401 58744 79/47 81/49 82/50 83/51 84/51 85/52 85/52 227 341 455 569 684 798 912 12561 18842 25122 31403 37683 43964 50244 74/42 76/44 77/45 78/46 79/46 80/47 80/47 175 263 351 439 527 615 703 8753 13129 17506 21882 26258 30635 35011 65/33 67/35 68/36 69/37 70/37 71/38 71/38 CAP - Nominal capacity AF - Air flow Lw - Sound power level Lpa - Sound pressure level at 10 m Note: Performance data given for units with AC-motor fans, 400-3-50 power supply, refrigerant R-404A, Δt1 =15 K, operating pressure 26 bar, ENV327. For performance data for units with other refrigerants or fans, and for 09FCTE 90 dry coolers, see technical documentation or electronic selection program. Fan data Correction factors for different refrigerants Asynchronous Motors Diameter Speed* Wiring 6P 900 mm Number of poles H H L H L ∆ ∆ Y ∆ Y 8P 12P Power input Full load (kW) current (A) 2.2 5.3 1.3 3.5 0.8 1.7 0.5 1.5 0.25 0.65 Temperature difference ΔT, K Refrigerant 8 10 12 0.67 0.80 R-404A – R-22 – R-134a – R-507 0.53 0.46 0.62 0.77 R-407C, R-407A 15 1.00 1.00 17 1.13 1.15 20 1.33 1.38 ‘* H: High, L: Low Diameter 910 mm 910 mm Number of poles NA NA Speed (rpm) 1000 910 750 690 560 610 560 470 330 200 Wiring NA NA Power input (kW) 3.12 2.26 1.28 1.01 0.56 0.6 0.45 0.26 0.1 0.04 Full load current (A) 4.9 3.5 2.0 1.7 1.1 1.2 0.9 0.6 0.3 0.2 2209 EC-Motors A 2200 Single-row models Models 09TE 90 2MSB 09TE 90 3MSB 09TE 90 4MSB 09TE 90 5MSB 09TE 90 6MSB 09TE 90 7MSB 09TE 90 4MDB 09TE 90 6MDB 09TE 90 8MDB 09TE 90 10MDB 09TE 90 12MDB 09TE 90 14MDB 09TE 90 16MDB Max. length A, mm 2465 3590 4715 5840 6965 8090 2465 3590 4715 5840 6965 8090 9215 Net weight, kg 469 691 872 1072 1273 1472 882 1301 1650 2018 2390 2785 3256 1636 Dimensions and weights A Double-row models 69 1200