Test Drive carrier katalog | Page 47

30RB 162-802 Physical data 30RB 162-262 “B” and 30RB 302-802 units 162 182 202 232 262 302 Air conditioning application as per EN14511-3: 2013 kW 170 184 208 222 265 297 Nominal cooling capacity EER kW/kW 2.95 2.96 2.86 3.00 2.67 2.77 Eurovent class B B C B D C ESEER kW/kW 3.71 3.53 3.82 3.87 3.69 3.80 Hermetic scroll, 48.3 r/s Compressors R-410A Refrigerant* Pro-Dialog Plus Capacity control All aluminium micro-channel heat exchanger (MCHE) Condensers Axial Flying Bird 4 with rotating shroud Fans Quantity 3 4 4 4 4 5 342 372 402 432 462 522 602 672 732 802 331 2.69 D 3.81 366 2.80 C 3.95 395 2.60 D 3.72 422 2.71 C 3.71 452 2.59 D 3.65 503 2.58 D 3.56 607 2.72 C 3.97 657 2.68 D 3.88 712 2.59 D 3.75 774 2.58 D 3.71 5 6 6 7 7 8 9 10 11 12 31597 31597 36111 40623 45139 49653 54167 Total air flow (high speed) l/s 13542 18056 18056 18056 18056 22569 22569 27083 27083 Twin-circuit plate heat exchanger Direct expansion, shell-and-tube Evaporator Dimensions** mm 2457 x 2253 x 2297 3604 x 3353 x 2297 Length x depth x height NOTE: For the conditions, please refer to page 31. For 30RB 162-262 units with option 280 (shell-and-tube heat exchanger) please refer to the specific product literature * Weight shown is a guideline only. F