Test Drive carrier katalog | Page 45
30RBSY 039-160
Physical data
30RBSY
039
045
050
060
070
080
090
100
Air conditioning application as per EN14511-3 : 2013
Condition 1
kW
39.6
44.0
51.2
58.1
66.2
77.7
86.7
97.1
Nominal cooling capacity
EER
kW/kW
2.93
2.81
2.66
2.7
2.68
2.65
2.71
2.72
Eurovent class
A
A
B
A
B
B
A
A
ESEER
kW/kW
3.93
4.04
3.98
3.9
3.72
3.75
3.86
3.89
Condition 2
kW
53.0
58.9
68.5
80.9
83.6
97.0
114.4
126.5
Nominal cooling capacity
EER
kW/kW
3.50
3.38
3.14
3.36
2.91
2.99
3.16
3.08
Operating weight (with MCHE heat exhangers)*
Standard unit without hydronic module kg
450
458
461
473
473
491
785
795
Standard unit with hydronic module
Single high-pressure pump
kg
480
488
491
503
503
521
817
827
Dual high-pressure pump
kg
506
513
516
528
529
547
862
872
Hermetic scroll compressors, 48.3 r/s
Compressors
Circuits A/B
2/2/2/2/2/2/3/3/R-410A
Refrigerant*
Pro-Dialog+
Capacity control
All aluminium micro-channel heat exchanger (MCHE)
Condensers
Axial Flying Bird IV with rotating shroud
Fans
Quantity
1
1
1
1
1
1
2
2
Total air flow (at high speed)
l/s
3800
3800
3800
3800
4600
4600
7600
7600
Direct expansion plate heat exchanger
Evaporator