[ Data Centres ]

[ Data Centres ]

Liquid cooling has moved from a niche solution to a baseline requirement for data centres.
temperature must span 17 ° C to 65 ° C, with 75 ° C increasingly requested as an option, shipping temperature – 40 ° C to 75 ° C, and the finished assembly must survive salt-spray corrosion testing( ASME B117 / ASTM B368) and shockand-vibration testing( ISTA 3-E) fully assembled and rack-mounted. Shelf life is set at five years and service life at ten. Flow velocity is capped at 1.5 m / s per ASHRAE guidance, to keep pressure drop and erosion in check across dozens of parallel server loops.
Materials that meet the requirements Choosing the right material is the first step in meeting these requirements. Stainless steel is one of the preferred materials on OCP’ s approved list for parts that come into contact with coolant. The listed grades include SS304( UNS S30403), SS316( UNS S31603), SS321, and SS410.
Common manifold tube grades, such as EN 1.4301 / 1.4307( AISI 304 / 304L) and EN 1.4404( AISI 316L), meet these specifications. They are also compatible with the propylene glycol and OATbased coolants commonly used in secondary cooling loops. 304 / 304L delivers the corrosion resistance, weldability, and formability required for high-volume, roll-formed products, while 316L adds enhanced resistance to chlorides for installations exposed to more aggressive makeup water, humid climates, or coastal sites. For projects where weight and wall thickness are critical constraints, EN 1.4162 lean duplex offers higher mechanical strength, allowing thinner walls without sacrificing the safety margin required by 3x-burst-pressure specifications. This combination of high strength and low weight is especially useful for large manifolds serving GPU racks with 40 or more server loops. It also reduces the weight mounted behind fully loaded cabinets.
Leak-free from the seam up with laser welding Nothing in Table 1 matters if the tube itself leaks or restricts flow. Manifold tubes are typically produced using high-precision laser welding along the longitudinal seam, resulting in a narrow, strong, virtually spatter-free weld with a minimal heat-affected zone. Two things follow directly from this. First, a smooth inner surface maintains a stable, predictable pressure drop throughout the manifold. This is checked through OCP flowresistance and flow-distribution tests. Second, clean welds reduce defects that could cause leaks. Every rack manifold must pass leak tests in accordance with ASME E1003, E499,
EN designation AISI equivalent Key property Best suited for
1.4301 / 1.4307 304 / 304L Corrosion resistance, formability, weldability Standard-duty manifolds; OCP wetted-materials baseline
1.4404 316L Enhanced chloride / pitting resistance Humid, coastal or aggressive make-up-water sites
1.4162
Lean Duplex
Higher mechanical strength at lower wall
thickness
Tall, dense VRMs; weight-critical rack designs
Table 1. Qualification list