Protection Engineering Basics and Schemes Protection Engineering | Page 25

1.1.8.1 Method:  Take one conductor  Take CT need to be tested  CT must not be placed in any circuit , but at your Testing facility or near Testing equipment  Place your conductor in air gap of CT  Take One battery and in series of battery connect one push button , then connect the terminals to the Conductor  Your Ammeter (dynamo Type) will be connect with both terminals of Secondary  While this arrangement completer , press push button which you knew remain open till press, when you press push button , the dynamo type ammeter show flicking of needle from zero value to positive value , and when you release your push button ,needle flick towards negative value then it’s means your CT polarity is correct and in that same position you need to connect your CT to test block, but let suppose when you press push button if the needles show no flicking toward positive value or move toward negative value or remain jam on zero position it’s means polarity is incorrect. pg. 25