Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 47

Product Information FIRESTOP PUTTY PAD CFS-P PA Product description • A moldable firestop putty designed to help protect electrical outlet boxes Product features • • • • No expiration date alleviates shelf life concerns No tools required A moldable firestop putty designed to help protect electrical outlet boxes Can be used for commercial and residential applications Acoustically rated drywall - sound transmission classification 59 according to ASTM E90-97 based on specific construction Quick and simple to install Applied by hand, no tools required No electrical conductivity Paper backing may be left on one side • • • • • Areas of application • Protection of electrical outlet boxes • Acoustically rated drywall • Commercial and residential applications For use with • Gypsum wall assemblies with wood or metal studs Examples • Where two outlets are within a single stud/cavity or within 24" measured horizontally (not back to back unless specified by the specific UL approval) Installation instructions Technical Data Consistency Moldable putty Color Red Application temperature 40°F (5°C) to 95°F (35°C) Storage temperature 40°F (5°C) to 104°F (40°C) Curing time Non-curing Density 1.48 g/cm 3 Intumescent activation Approx. 220°F to 250°F (104°C to 121°C) Volatile solvents None Asbestos fibers None Surface burning characteristics (ASTM E 84-96) Flame Spread: 15 Smoke development: 10 Sound transmission classification (ASTM E 90-97) 59 (Relates to specific construction) Tested in accordance with UL 263, ASTM E 84, ASTM G21 FM $33529(' )RU3HQHWUDWLRQ)LUH6WRSV &RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLG 6 x 7 x 3/16 in 7-1/4 x 7-1/4 x 3/16 in 9-1/4 x 9-1/4 x 3/16 in Dimensions (LxWxH) WALL OPENING PROTECTIVE MATERIAL FIRE RESISTANCE CLASSIFICATION SEE PRODUCT CATEGORY IN UL FIRE RESISTANCE DIRECTORY 66Y7 • See Hilti Literature or third-party listings for complete application and installation details R FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, INC Hilti FOR Firestop USE IN TROUGH-PENETRATION FIRESTOP SYSTEMS Saving lives SEE UL innovation FIRE RESISTANCE DIRECTOR through 66Y7 and education 45