Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 46

FIRESTOP BOARD CP 675T Product description • Ready to use Firestop Board designed for medium to large openings with cable trays and multiple penetrations Product features • • • • • • • • • • No expiration date alleviates shelf life concerns Lightweight design Satisfies a wide range of application scenarios Allows for high flexibility and eases re-penetration/cable mining from one side of the wall Easy and fast cable re-penetration and cable mining with reduced labor and materials L abor saving “one person, one sided installation” method Polyurethane foam material, easy to cut without electric tools No dust, no fibers, no mess Same system for all types of wall materials May be used in conjunction with CFS-BL Firestop Block Areas of application • Temporary or permanent sealing of cables and cable tray penetrations • Sealing single or multiple penetrations in large openings • Temporary or permanent sealing of large blank openings For use with • Concrete, concrete block, and gypsum wall assemblies • Concrete floor assemblies Examples • Locations where telecommunications and electrical applications are modified on a regular basis such as central office facilities, computer data centers, commercial buildings, healthcare facilities, and laboratories • New buildings under construction and during renovation Installation instructions • See Hilti Literature or third-party listings for complete application and installation details FIRESTOP DEVICE FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 5N76 FM Technical Data Color Red Dimensions (LxWxH) 26" x 39" x 1" (Large Board) (660 mm x 990 mm x 25 mm) 26" x 28" x 1" (Small Board) (660 mm x 711 mm x 25 mm) Density 320 kg/m 3 Application temperature -22°F to 176°F (-30°C to 80°C) Temperature resistance -22°F to 176°F (-30°C to 80°C) Surface burning characteristics (ASTM E 84-00) Flame Spread Index: 5 Smoke Development Index: 10 Mold and mildew (ASTM G-21) Mold and Mildew Resistant Approvals California State Fire Marshall - No. 4485-1200:125 Tested in accordance with UL 1479, ASTM E 814, ASTM E 84, ASTM G21, CAN/ULC-S115 $33529(' )RU3HQHWUDWLRQ)LUH6WRSV &RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH Hilti Firestop Saving lives through innovation and MATERIALS education FILL, VOID OR CAVITY CLASSIFIED BY UNDERWRITERS LABORATORIES, INC. 44 FOR USE IN TROUGH-PENETRATION R FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY