Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 46
FIRESTOP BOARD CP 675T
Product description
• Ready to use Firestop Board designed for medium to large openings with cable
trays and multiple penetrations
Product features
•
•
•
•
•
•
•
•
•
•
No expiration date alleviates shelf life concerns
Lightweight design
Satisfies a wide range of application scenarios
Allows for high flexibility and eases re-penetration/cable mining from one side
of the wall
Easy and fast cable re-penetration and cable mining with reduced labor and
materials
L abor saving “one person, one sided installation” method
Polyurethane foam material, easy to cut without electric tools
No dust, no fibers, no mess
Same system for all types of wall materials
May be used in conjunction with CFS-BL Firestop Block
Areas of application
• Temporary or permanent sealing of cables and cable tray penetrations
• Sealing single or multiple penetrations in large openings
• Temporary or permanent sealing of large blank openings
For use with
• Concrete, concrete block, and gypsum wall assemblies
• Concrete floor assemblies
Examples
• Locations where telecommunications and electrical applications are modified
on a regular basis such as central office facilities, computer data centers,
commercial buildings, healthcare facilities, and laboratories
• New buildings under construction and during renovation
Installation instructions
• See Hilti Literature or third-party listings for complete application and
installation details
FIRESTOP DEVICE
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
5N76
FM
Technical Data
Color Red
Dimensions (LxWxH) 26" x 39" x 1" (Large Board)
(660 mm x 990 mm x 25 mm)
26" x 28" x 1" (Small Board)
(660 mm x 711 mm x 25 mm)
Density 320 kg/m 3
Application temperature -22°F to 176°F (-30°C to 80°C)
Temperature resistance -22°F to 176°F (-30°C to 80°C)
Surface burning characteristics
(ASTM E 84-00) Flame Spread Index: 5
Smoke Development Index: 10
Mold and mildew (ASTM G-21) Mold and Mildew Resistant
Approvals California State Fire Marshall -
No. 4485-1200:125
Tested in accordance with UL 1479, ASTM E 814, ASTM E 84, ASTM G21,
CAN/ULC-S115
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
Hilti Firestop
Saving lives
through innovation
and MATERIALS
education
FILL, VOID OR CAVITY
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
44
FOR USE IN TROUGH-PENETRATION
R
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY