FIRESTOP PUTTY PAD CFS-P PA
Product description
• A moldable firestop putty designed to help protect electrical outlet boxes
Product features
•
•
•
•
No expiration date alleviates shelf life concerns
No tools required
A moldable firestop putty designed to help protect electrical outlet boxes
Can be used for commercial and residential applications
Acoustically rated drywall - sound transmission classification 59 according to
ASTM E90-97 based on specific construction
Quick and simple to install
Applied by hand, no tools required
No electrical conductivity
Paper backing may be left on one side
•
•
•
•
•
Areas of application
• Protection of electrical outlet boxes
• Acoustically rated drywall
• Commercial and residential applications
For use with
• Gypsum wall assemblies with wood or metal studs
Examples
• Where two outlets are within a single stud/cavity or within 24" measured
horizontally (not back to back unless specified by the specific UL approval)
Installation instructions
Technical Data
Consistency Moldable putty
Color Red
Application temperature 40°F (5°C) to 95°F (35°C)
Storage temperature 40°F (5°C) to 104°F (40°C)
Curing time Non-curing
Density 1.48 g/cm 3
Intumescent activation Approx. 220°F to 250°F (104°C to 121°C)
Volatile solvents None
Asbestos fibers None
Surface burning characteristics
(ASTM E 84-96) Flame Spread: 15
Smoke development: 10
Sound transmission classification
(ASTM E 90-97) 59 (Relates to specific construction)
Tested in accordance with UL 263, ASTM E 84, ASTM G21
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLG
6 x 7 x 3/16 in
7-1/4 x 7-1/4 x 3/16 in
9-1/4 x 9-1/4 x 3/16 in
Dimensions (LxWxH)
WALL OPENING PROTECTIVE
MATERIAL
FIRE RESISTANCE CLASSIFICATION
SEE PRODUCT CATEGORY IN
UL FIRE RESISTANCE DIRECTORY
66Y7
• See Hilti Literature or third-party listings for complete application and
installation details
R
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC